OPC DA Diagnozer

A read-only Windows service that acts as an independent OPC DA reference client to diagnose disconnections, communication latency, and data-quality problems between a SCADA system and a control system communicating over OPC DA.

It continuously connects to the OPC DA server, polls a pre-defined list of tags, and reports every anomaly with precise timestamps — unnatural read latencies, DCOM disconnects, hung RPC calls, tags marked BAD/UNCERTAIN, stale timestamps, frozen values, and flapping quality — as structured events (JSONL logs, Windows Event Log, optional HTTP webhook).

Status: planning. Read the specification and the implementation plan first.

Why

OPC DA failures are notoriously hard to pin down because they hide behind generic COM errors, calls that hang with no timeout, or silently degraded item quality. This tool answers the triage question where is the problem? with evidence:

Observation from the Diagnozer Most likely problem location
Clean reads while SCADA complains SCADA host itself (DCOM perms, CPU, its own load)
Diagnozer also sees disconnects/RPC errors Shared path: network, firewall, DCOM, OPC server host
Connection stable but many tags BAD_COMM_FAILURE Link between OPC server and the control devices
Hangs without errors Silent network drop (firewall/MTU) — classic DCOM pitfall

See the full interpretation matrix in the specification.

Planned features

  • Windows service (auto-start, SCM crash recovery) with a foreground run mode for testing
  • Local or remote (DCOM) connections to any OPC DA server
  • Server browsing: list-servers (discovery), list-devices and list-tags (address-space walk) — live now
  • Latency monitoring: spikes, streaks, and p95 trends against configurable thresholds
  • Hang watchdog: flags RPC calls that never return — the silent killer
  • Quality monitoring: BAD/UNCERTAIN transitions with decoded subcodes, persistent-bad and flapping detection, mass-degradation alarm
  • Staleness & frozen-value detection while quality still reports GOOD
  • Structured events: rotating JSONL, Windows Event Log, optional HTTP webhook
  • Strictly read-only; single group, modest poll rate — does not perturb the measured system

Quick start

# list the OPC DA servers available locally (or on a DCOM host with --host)
opcda-diagnozer list-servers
opcda-diagnozer list-servers --host CONTROL-HOST01        # remote, via DCOM
opcda-diagnozer list-servers --source registry --json     # no-COM local scan

# list the devices (address-space branches) of the configured server
opcda-diagnozer list-devices
opcda-diagnozer list-devices --depth 2                    # include sub-devices
opcda-diagnozer list-devices --json                       # script-friendly output

# list the tags of one device (the item_id values go into config `tags:`)
opcda-diagnozer list-tags "Simulation Items.Bucket Brigade"
opcda-diagnozer list-tags "Simulation Items" "Bucket Brigade"   # equivalent
opcda-diagnozer list-tags --recursive "Simulation Items"  # whole subtree
opcda-diagnozer list-tags                                 # every tag on the server

# validate config
opcda-diagnozer check-config

# connect once and read every configured tag, print results
opcda-diagnozer probe

# foreground run (console) — best for first deployment validation
opcda-diagnozer run

# install as Windows service (dedicated account required for DCOM auth)
opcda-diagnozer install --account DOMAIN\svc-opcdiag

list-servers uses two discovery mechanisms (--source): the OPC DA Automation Wrapper's GetOPCServers over COM (works remotely via DCOM; needs Launch+Activation permissions on the target host), and a local COM-registration scan that reads the OPC DA component categories directly from the registry — no COM, useful on locked-down hosts or when the wrapper DLL is not registered. auto tries the first, falls back to the second. Note the bitness rule still applies: a 32-bit process enumerates the 32-bit registry view — exactly the servers this tool can load.

list-devices / list-tags browse the connected server's address space through the Automation Wrapper's browser (CreateBrowser): devices are branches, tags are leaves. They work locally and over DCOM (same Launch+Activation requirements). A device path is either one dotted string ("Simulation Items.Bucket Brigade") or several quoted branch names — use the latter when a branch name itself contains a dot. On flat-namespace servers (organization: flat) every tag hangs directly off the root; list-tags without a device lists them all.

Configuration example (config.example.yaml)

opc:
  server: "Matrikon.OPC.Simulation.1"   # server ProgID
  host: "CONTROL-HOST01"                # DCOM host; omit for local
  connect_timeout_s: 10

poll:
  interval_s: 1.0
  timeout_ms: 5000                      # beyond this the call is flagged as a hang

tags:
  - { name: "Channel1.Device1.Counter", expect_change: true }
  - { name: "Channel1.Device1.Level" }

latency:
  warn_ms: 1000
  critical_ms: 5000
  slow_poll_streak: 5
  window_polls: 60

quality:
  persistent_bad_s: 30
  flapping_transitions_per_window: 5

stale:
  enabled: true
  max_age_s: 120

report:
  heartbeat_s: 300
  jsonl:  { dir: "C:/ProgramData/OPCDA-Diagnozer/logs", max_mb: 50, backups: 10 }
  eventlog: { source: "OPCDA-Diagnozer", min_severity: WARN }

DCOM troubleshooting quick reference

Setup checklist for the service account (both hosts):

  1. dcomcnfg → Component Services → DCOM Config → the OPC server → Properties:
    • Security → Launch & Activation: allow Remote Activation for the service account.
    • Security → Access Permissions: allow Local + Remote access.
    • Identity: prefer a dedicated account over "Launching user".
  2. Firewall on the OPC server host: TCP 135 (RPC endpoint mapper) + the RPC dynamic port range (optionally restricted via netsh int ipv4 set dynamicport tcp ...).
  3. NTP time sync on both hosts — OPC DA timestamps and staleness detection depend on it.
  4. Be aware of post-2022 Windows DCOM hardening (KB5004442 family): DCOM activation requires explicit authentication and may break legacy OPC setups with E_ACCESSDENIED-type failures.

Common HRESULTs the tool decodes and reports:

HRESULT Meaning
0x800706BA RPC server unavailable — server process down, firewall, or DCOM activation refused
0x800706BE RPC call failed mid-flight — server crashed or connection reset
0x80010108 Object disconnected from clients — OPC server dropped us (crash/restart)
0x80070005 Access denied — DCOM security misconfiguration
0x80040154 Class not registered — wrong ProgID, or wrapper/server registered under a different bitness
0xC0040007 Invalid item ID — tag name wrong in config (surfaced by probe)

Bitness warning: the OPC DA Automation Wrapper (OPCAutomation.dll) and the Graybox wrapper are typically 32-bit in-proc DLLs — the Python interpreter must match (32-bit). This is decided and verified in Phase 0 of the implementation plan.

Safety

  • The tool never writes to the OPC server — there is no write path in the code.
  • It uses one OPC group and a static, small tag list at a modest poll rate (default 1 s) so it does not load the system it is measuring.

Development setup

The OPC DA wrappers (OPCAutomation.dll, GBDaCtl.dll) are 32-bit in-proc COM DLLs, so the Python interpreter must be 32-bit (SPECIFICATION §11 / Phase 0 decision).

# create the 32-bit venv (requires the 32-bit Python installed via the py launcher)
& "C:\Users\<user>\AppData\Local\Programs\Python\Python314-32\python.exe" -m venv .venv
& ".\.venv\Scripts\python.exe" -m pip install -e ".[dev]"

# verify bitness — must print 32
& ".\.venv\Scripts\python.exe" -c "import struct; print(struct.calcsize('P') * 8)"

# run the (COM-free) unit + fake-integration tests
& ".\.venv\Scripts\python.exe" -m pytest

Notes:

  • Dependencies are chosen to be installable without a C compiler: ruamel.yaml (pure Python) is used instead of PyYAML, which publishes no 32-bit CPython 3.14 wheels and whose sdist requires MSVC.
  • COM-dependent modules (Automation Wrapper, Event Log, service) are import-guarded; the unit test suite runs on any OS via the in-process fake client (opcda_diagnozer.opc.fake).
  • 32-bit CPython can be installed with the Python Install Manager (py install 3.14 -a x86) or the installer from python.org ("Download Windows installer (32-bit)").