# OPC DA Diagnozer — Implementation Plan
Companion to [`docs/SPECIFICATION.md`](SPECIFICATION.md). Targets **v1.0** as the first
production-deployable release.
---
## 1. Milestones
| Milestone | Content | Exit condition |
|-----------|---------|----------------|
| **v0.1 — Foreground proof** | CLI reads configured tags once per second in a console, prints events | Successfully reads from a real (or simulation) OPC DA server |
| **v0.2 — Detection engine** | All detectors (D1–D15), event model, JSONL logging | Unit tests green; chaos scenarios produce correct events |
| **v0.5 — Windows service** | pywin32 service, watchdog/hang recovery, Event Log, CLI install/run | Runs unattended through reboot + server-kill test |
| **v1.0 — Production** | Packaging, runbook, 24 h soak, optional webhook | Acceptance criteria AC1–AC10 (spec §13) met |
## 2. Project layout
```
opcda-diagnozer/
├── README.md
├── pyproject.toml
├── config.example.yaml
├── docs/
│ ├── SPECIFICATION.md
│ └── IMPLEMENTATION_PLAN.md
├── src/opcda_diagnozer/
│ ├── __init__.py
│ ├── __main__.py # python -m opcda_diagnozer
│ ├── main.py # CLI: run / install / uninstall / check-config / probe / list-devices / list-tags
│ ├── config.py # pydantic-free typed config (dataclasses) + YAML load + validation
│ ├── events.py # DiagEvent, Severity, EventKind
│ ├── quality.py # OPC DA quality decode tables
│ ├── opc/
│ │ ├── base.py # OpcClient + Browser protocols, ReadResult, OpcError(hresult)
│ │ ├── discovery.py # list-servers: Automation GetOPCServers / registry scan
│ │ ├── browse.py # list-devices/list-tags: address-space walk (branches/leaves)
│ │ ├── automation.py # OPC DA Automation Wrapper adapter (OPCAutomation.dll)
│ │ └── fake.py # in-process fake client + fake address space (tests, demo)
│ ├── monitor/
│ │ ├── state.py # connection state machine + backoff
│ │ ├── poller.py # COM thread: connect → poll loop → feed detectors
│ │ └── detectors.py # D1–D15 rule implementations
│ ├── report/
│ │ ├── base.py # Reporter protocol
│ │ ├── jsonl.py # rotating JSONL file
│ │ ├── eventlog.py # Windows Event Log (WARN+)
│ │ └── http.py # optional webhook
│ └── service.py # pywin32 ServiceFramework wrapper
└── tests/
├── test_quality.py
├── test_detectors.py
├── test_state.py
├── test_config.py
└── test_poller_fake.py # end-to-end against opc.fake, no COM needed
```
## 3. Phase 0 — Feasibility & environment (≈0.5–1 day)
**Goal:** validate the COM access strategy against reality before building anything.
Tasks:
1. Identify target OPC DA server: ProgID, host, DA version, bitness (32/64-bit EXE?).
2. Choose wrapper backend:
- **A. OPC DA Automation Wrapper** (`OPCAutomation.dll`) — ubiquitous in industry,
ships with many SCADA installs; likely default.
- **B. OpenOPC / Graybox wrapper** (`GBDaCtl.dll`) — fallback.
- Note: both are typically **32-bit in-proc DLLs** → client Python must be 32-bit
(see spec §11). Decide interpreter bitness here.
3. Stand up a **test server** (Matrikon OPC Simulation Server, KepServerEX demo, or the
actual control-system server in a maintenance window) and successfully read one tag
from Python (`win32com.client.Dispatch`).
4. Verify DCOM configuration for the service account (`dcomcnfg`: Launch/Activation →
Remote Activation; Access → Local+Remote). Record required firewall ports
(TCP 135 + RPC dynamic range).
5. Record baseline behavior: normal read RTT, quality values, what error the wrapper
surfaces when the server is stopped (feeds D1 implementation).
**Exit:** a throwaway script reads ≥ 3 tags from the remote server with measured RTT.
## 4. Phase 1 — Core engine (≈2–3 days)
1. `config.py` — YAML config (see `config.example.yaml` sketch in README), dataclass
model, strict validation, `check-config` messages that explain exactly what is wrong.
2. `quality.py` — decode tables (spec §7), `decode_quality(raw: int) -> QualityInfo`.
3. `opc/base.py` — client abstraction:
```python
class OpcClient(Protocol):
def connect(self) -> None: ...
def read(self, tags: Sequence[str]) -> list[ReadResult]: ...
def close(self) -> None: ...
```
`ReadResult`: `tag, value, quality_raw, device_time, error` — plus per-call RTT
measured by the poller. COM errors are normalized to `OpcError` carrying the raw
`HRESULT` + decoded name.
4. `opc/automation.py` — Automation Wrapper adapter (single group, static items,
`SyncRead`); every COM exception mapped to `OpcError` with `win32com` scode.
5. `monitor/state.py` — state machine (spec §10.2), backoff, reconnect accounting.
6. `monitor/detectors.py` — D1–D15 as small pure functions/classes over
`PollOutcome` (list[ReadResult] + rtt_ms + error), using an injected clock for
testability. Rolling window (deque, size `window_polls`) for p95/streak logic.
7. `monitor/poller.py` — the single COM thread; watchdog logic for hang detection
(spec §10.4): a second thread timestamps poll starts/ends; on `hard_hang_s` the COM
thread is abandoned and rebuilt.
8. `events.py` — event dataclass + JSON serialization.
9. `opc/fake.py` — scriptable fake client (sequences of outcomes: good reads, errors,
hangs, quality flips) → powers the entire unit-test suite without COM/hardware.
**Exit:** `opcda-diagnozer run` (foreground console) produces correct events against the
fake client; unit tests for all detectors.
## 5. Phase 2 — Reporters (≈1 day)
1. `report/jsonl.py` — rotation (size + backups), atomic-ish append, header line with
config digest for provenance.
2. `report/eventlog.py` — pywin32 `win32evtlog` usage; map severities; source
registration via `install` step.
3. `report/http.py` — optional webhook with timeout + simple retry/drop on failure
(never blocks the poll loop; queue with bound).
4. Heartbeat assembly (D15): uptime, reconnects, RTT percentiles, tags-bad counts.
**Exit:** events visible in file + Event Log; heartbeat cadence verified.
## 6. Phase 3 — Windows service (≈1 day)
1. `service.py` — `win32serviceutil.ServiceFramework`; service host thread spawns the
COM worker; clean `stop` handling (`SetServiceStatus STOP_PENDING`, join with
timeout, abandon hung COM thread on shutdown).
2. CLI verbs: `install /uninstall /start /stop` (wraps `sc.exe` semantics),
`run` (foreground), `check-config`, `probe` (connect once, print one read),
`list-items` (browse validation tool).
3. SCM recovery config (`sc failure ... restart`), auto-start, service account
documentation.
4. Config/log default dir: `%ProgramData%\OPCDA-Diagnozer\`.
**Exit:** survives reboot; survives OPC-server kill (produces D1/D2 events, reconnects);
`probe` and `check-config` give usable diagnostics to an ops engineer.
## 7. Phase 4 — Integration & chaos testing (≈1–2 days)
Scenario matrix against a simulation server (and, when available, the real server):
| Scenario | How to inject | Expected events |
|----------|---------------|-----------------|
| Server process killed | `taskkill` | D1 (HRESULT), D2 with outage duration |
| Server service stopped/restarted | `net stop/start` | D1, D2 |
| Firewall drop (silent) | block outbound RPC ports / pull NIC | D7 hang, then D1 |
| Latency injection | Clumsy / `netsh` delay | D4 spikes, D5 streak, D6 trend |
| Device comm failure | simulation server "communication disturbance" items | D8 with `BAD_COMM_FAILURE`, D10 persistence |
| Quality oscillation | toggling sim items | D11 flapping |
| Stale/frozen tag | simulation server static item marked `expect_change` | D12 / D13 |
| Mass bad quality | all sim items to bad | D14 |
| Config errors | bad ProgID, unknown tag | fast fail + actionable message; `OPC_E_INVALIDITEMID` surfaced at startup |
| Soak | 24 h healthy run | no leaks, heartbeats every 5 min, zero false positives |
**Exit:** each row verified manually against the event log; AC2/AC3/AC4/AC5 confirmed.
## 8. Phase 5 — Packaging & docs (≈0.5–1 day)
- `pyproject.toml` wheel installable with pip into the chosen (32-bit) Python;
document the on-host install procedure (PyInstaller packaging for pywin32 services is
fragile — deferred).
- `README.md` finalized (install, config, DCOM checklist, HRESULT table).
- Ops runbook: how to read events, what each kind means (link to spec §12 matrix),
how to reconfigure thresholds, where evidence lives.
- Version 1.0.0 tag.
## 9. Testing strategy
- **Unit** (no COM): detectors against scripted `PollOutcome` sequences with a fake
clock; quality decode; config validation; backoff/state transitions; JSONL rotation.
- **Integration:** `test_poller_fake.py` runs the full poller+reporters against
`opc.fake` in-process — the whole event pipeline without Windows COM.
- **Manual/chaos:** Phase 4 matrix (necessarily on Windows against a real/simulated
OPC DA server — cannot be automated in CI without the DCOM environment).
- CI: unit + fake-integration tests run on any OS (COM adapters are import-guarded);
chaos tests are a documented manual procedure.
## 10. Risk register
| Risk | Impact | Mitigation |
|------|--------|------------|
| Wrapper DLL bitness mismatch (32-bit only) | Cannot load wrapper | Phase 0 decision; use 32-bit Python; keep client abstraction so backend can be swapped |
| Automation Wrapper not present on diag host | No COM access | Phase 0 check; ship/distribute wrapper install in runbook (vendor redistribution rules apply) |
| DCOM hardening (KB5004442) blocks activation | Connect fails with `E_ACCESSDENIED`/activation errors | Runbook covers `dcomcnfg` steps; events surface raw HRESULT |
| COM calls hang indefinitely | Service appears alive but blind | Explicit watchdog + thread recycling (spec §10.4) |
| COM apartment violations (cross-thread calls) | Random `RPC_E_WRONG_THREAD` crashes | Single dedicated COM thread; all COM handles stay on it |
| Our client perturbs the system | Skewed diagnosis | One group, static small tag list, 1 s default poll, read-only |
| pywin32 service + COM quirks (GIL, STA init) | Service instability | Phase 3 spike; foreground `run` mode always available as fallback |
| Tag list too large / wrong item IDs | Noise, misleading RTT | `probe` + `check-config` validate up-front; per-poll error accounting |
| SCADA/host clock skew | Misleading staleness events | Local receive time always recorded; `max_age_s` configurable |
## 11. Effort estimate
| Phase | Estimate |
|-------|----------|
| 0 Feasibility | 0.5–1 d |
| 1 Core engine | 2–3 d |
| 2 Reporters | 1 d |
| 3 Service | 1 d |
| 4 Chaos testing | 1–2 d |
| 5 Packaging/docs | 0.5–1 d |
| **Total v1.0** | **≈ 6–9 days** |
## 12. Definition of done (v1.0)
- All Phase 4 scenarios pass; AC1–AC10 (spec §13) verified.
- 24 h soak clean.
- README + runbook complete enough for an ops engineer to deploy unaided.
- Code reviewed; no write path to OPC anywhere in the codebase.
- Config example covers every configurable threshold.
+263
View File
@@ -0,0 +1,263 @@
# OPC DA Diagnozer — Project Specification
**Version:** 0.1 (draft)
**Status:** Planning
**Target platform:** Windows only (OPC DA is a COM/DCOM technology)
---
## 1. Problem statement
We experience intermittent **disconnections** and/or **high communication latency** between a
SCADA system and a control system that communicate over **OPC DA** (Data Access, the
COM/DCOM-based predecessor of OPC UA). Today we have no objective evidence to answer the
key triage question:
> *Is the problem in the SCADA host, the network/DCOM layer, the OPC DA server, or the
> link between the OPC server and the control devices?*
OPC DA failure modes are notoriously hard to diagnose because failures surface as generic
`HRESULT` errors, hung calls with **no client-side timeout**, or silently degraded item
quality — long before the SCADA operator sees anything.
## 2. Approach
Deploy an **independent, read-only OPC DA reference client** that continuously exercises
the same path the SCADA uses:
- Connect to the OPC DA server (local or remote via DCOM) from a Windows machine.
- Poll a small, pre-defined list of tags at a fixed interval.
- Measure **read round-trip time (RTT)**, track **item quality** (GOOD / UNCERTAIN / BAD
and subcodes), **device timestamps**, and **connection state**.
- Emit structured, timestamped **diagnostic events** whenever anything deviates from
normal — disconnects, slow reads, hung calls, quality degradation, frozen/stale values.
Because the client is independent of the SCADA, its observations provide a **reference
baseline** against which the SCADA's complaints can be triangulated (see §12).
## 3. Deployment architecture
```mermaid
flowchart LR
subgraph SCADAzone["SCADA zone (or dedicated diag host)"]
DIAG["OPC DA Diagnozer<br/>(Windows service)"]
end
subgraph CTL["Control system / OPC DA server host"]
OPC["OPC DA server<br/>(COM/DCOM out-of-proc)"]
DEV["Control devices / PLC link"]
end
DIAG -- "DCOM reads (RPC 135 + dynamic ports)" --> OPC
OPC -.-> DEV
DIAG -- "Events (JSONL / Event Log / HTTP)" --> OPS["Engineers & monitoring"]
```
Placement note: run the tool **as close to the SCADA machine as possible** (same host or
same network segment) so its measured latencies are comparable to what the SCADA
experiences. Optionally run a second instance next to the OPC server host for differential
diagnosis.
## 4. Goals
1. Run unattended as a **Windows service** (auto-start, SCM crash recovery).
2. Connect to a configured OPC DA server (local or remote DCOM) and read a configured tag list.
3. Detect and report, with precise timestamps:
- disconnections and reconnects (including DCOM error codes),
- hung / timed-out RPC calls,
- read latencies exceeding thresholds (single spikes, streaks, and trends),
- tags whose quality is BAD or UNCERTAIN (with decoded subcode),
- persistent-bad and flapping (oscillating) quality per tag,
- stale device timestamps / frozen values while quality reports GOOD,
- mass quality degradation (many tags BAD at once → control-link problem).
4. Produce durable, machine-readable evidence (structured logs + Windows Event Log +
optional HTTP webhook) suitable for incident review and correlation.
5. Be **strictly read-only** and lightweight — must not perturb the system it measures.
## 5. Non-goals (v1)
- No writes to the OPC server (no `Write` code path at all).
- No OPC UA, OPC HDA, or Alarms & Events support.
- No data historian / storage of every sample (only events + periodic summaries).
- No UI/dashboard in v1 (JSONL logs + webhook are enough for Loki/Grafana ingestion).
- No automatic remediation (diagnose only).
## 6. Detection rules
| ID | Condition | Default rule | Severity |
|----|-----------|--------------|----------|
| D1 | Connection lost | Any read/connect COM failure | CRITICAL (event incl. decoded HRESULT) |
| D2 | Reconnect succeeded | After D1, reconnect works | INFO (event with outage duration) |
| D3 | Reconnect flapping | > 3 disconnects in 10 min | CRITICAL |
| D4 | Slow poll (spike) | Single read RTT > `warn_ms` (default 1000) | WARN |
| D5 | Sustained slow polls | RTT > `warn_ms` for `slow_poll_streak` (5) consecutive polls | CRITICAL |
| D6 | Latency trend | p95 RTT over last `window_polls` (60) > `warn_ms` | WARN |
| D7 | Poll hang | Read call does not return within `timeout_ms` (5000) — see §10.4 | CRITICAL (immediate), see recovery behavior |
| D8 | Tag quality → BAD | Any transition into BAD, decoded subcode | WARN (per tag) |
| D9 | Tag quality → UNCERTAIN | Any transition into UNCERTAIN | INFO |
| D10 | Persistent bad tag | Single tag BAD longer than `persistent_bad_s` (30) | WARN (escalated from D8) |
| D11 | Quality flapping | > 5 quality transitions for one tag within 10 min | WARN |
| D12 | Stale timestamp | Device timestamp older than `max_age_s` (120) while quality GOOD | WARN |
| D13 | Frozen value | `expect_change: true` tag with unchanged value+timestamp for `max_age_s` | WARN |
| D14 | Mass quality degradation | ≥ 50% of monitored tags BAD simultaneously while connection OK | CRITICAL (`CONTROL_LINK_DEGRADED` — points at OPC-server↔device link, not DCOM) |
| D15 | Heartbeat / summary | Periodic stats snapshot every `heartbeat_s` (300) | INFO |
All thresholds are configurable; severities are INFO / WARN / CRITICAL.
## 7. OPC DA quality codes (reference)
OPC DA quality is a 16-bit field. Bits 7–6 of the low byte give the class:
`0xC0` GOOD, `0x40` UNCERTAIN, `0x00` BAD. Bits 5–0 are the substatus. Values the tool
decodes and names:
| Code | Meaning |
|------|---------|
| `0xC0` | GOOD |
| `0xD8` | GOOD / local override |
| `0x44` | UNCERTAIN / last usable value |
| `0x40` | UNCERTAIN (unspecified) |
| `0x00` | BAD (unspecified) |
| `0x04` | BAD / configuration error |
| `0x08` | BAD / not connected |
| `0x0C` | BAD / device failure |
| `0x10` | BAD / sensor failure |
| `0x14` | BAD / last known value |
| `0x18` | BAD / communication failure |
| `0x1C` | BAD / out of service |
Remaining UNCERTAIN subcodes (DA 2.05a) are decoded by the same table in `quality.py`.
Every quality event carries the raw hex code **and** the decoded name.
## 8. Event model
Every event is a structured record:
```json
{
"time_utc": "2026-10-07T12:34:56.789Z",
"kind": "QUALITY_BAD",
"severity": "WARN",
"detail": {
"tag": "Channel1.Device1.Counter",
"quality_raw": "0x18",
"quality": "BAD_COMM_FAILURE",
"previous_quality": "GOOD",
"value": 1234.0,
"device_time_utc": "2026-10-07T12:34:55.100Z",
"rtt_ms": 42.1
},
"context": {
"uptime_s": 3600.5,
"reconnects_total": 2,
"rtt_p95_ms": 55.2,
"tags_bad": 3,
"tags_total": 25
}
}
```
`time_utc` is always the **local client receive time** (wall clock), so events remain
comparable even if the remote host's clock is wrong. Device timestamps are reported
alongside and clearly labeled.
## 9. Outputs (reporters)
| Reporter | Purpose | Notes |
|----------|---------|-------|
| JSONL rotating file | Primary evidence trail | One JSON event per line; rotation by size; default dir `%ProgramData%\OPCDA-Diagnozer\logs` |
| Windows Event Log | Ops visibility | WARN+ only; source `OPCDA-Diagnozer` |
| Console | Foreground/debug runs | Human-readable |
| HTTP webhook (optional) | Alert integration | POST one JSON event per request, optional bearer token |
Reporters are pluggable (`Reporter.emit(event)`); a heartbeat event every 5 minutes
proves liveness and enables baseline graphs even when everything is healthy.
## 10. Operational behavior
### 10.1 Run as a Windows service
- Registered via pywin32 (`opcda-diagnozer install`), auto-start, runs under a
**dedicated service account** (required for DCOM authentication, see §11).
- SCM recovery: restart on failure (first/second failure), plus internal watchdog.
### 10.2 Connection state machine
```mermaid
stateDiagram-v2
[*] --> Connecting
Connecting --> Connected : connect OK
Connecting --> ReconnectWait : COM error
Connected --> ReconnectWait : read error / hang
ReconnectWait --> Connecting : backoff elapsed
```
Reconnect backoff: exponential 1 s → 2 s → … capped at 60 s. Every disconnect/reconnect
pair is an event; outage duration is computed and reported.
### 10.3 COM apartment handling
All OPC/COM work runs on one dedicated STA thread inside the service process
(`pythoncom.CoInitialize()` on that thread only). Detectors run on the same thread (pure
Python, cheap); event reporting happens off-thread via a queue so slow I/O never blocks
polling.
### 10.4 The DCOM hang problem (important)
DCOM/RPC calls have **no client-side timeout**. If the network path breaks silently
(e.g., firewall drops), a read call can block for tens of seconds to minutes without
erroring. The tool handles this explicitly:
1. A watchdog flags a **poll hang** (D7) as soon as a call exceeds `timeout_ms`.
2. If the hang exceeds `hard_hang_s` (default 120 s), the service abandons the stuck
thread and creates a fresh connection on a new thread (stale `RPC` objects are
released by COM).
3. Hang events are distinguished from clean disconnects — this is often the smoking gun
for silent network drops.
### 10.5 Safety constraints
- Read-only by construction: no write API is called; the code has no write path.
- Single OPC group, static item list, modest poll rate (default 1 s) to keep added
server load negligible.
- Configuration errors fail fast at startup with actionable messages
(`opcda-diagnozer check-config` validates without connecting… and `--probe` connects
once and reports).
## 11. Environment & constraints
| Constraint | Consequence |
|------------|-------------|
| OPC DA is Windows/COM only | Service runs on Windows only (Server 2012 R2 … 2022, Win 10/11) |
| OPC DA wrappers are often **32-bit** DLLs (OPC DA Automation Wrapper `OPCAutomation.dll`, Graybox `GBDaCtl.dll`) | Python interpreter bitness must match the wrapper DLL — likely **32-bit Python** for v1; decision in Phase 0 |
| DCOM security | The service account needs Launch+Activation and Access permissions on the OPC server (via `dcomcnfg`); account must authenticate across the network (not `LocalSystem`) |
| Post-2022 Windows DCOM hardening (KB5004442 family) | DCOM activation now requires explicit authentication; legacy OPC setups may fail activation — errors must be reported clearly |
| RPC over TCP | Firewall: TCP 135 + RPC dynamic port range on the server host; misconfig shows up as `RPC_S_SERVER_UNAVAILABLE` |
| Clock skew | Device timestamps may be misleading; every event also carries local receive time; recommend NTP on both hosts |
## 12. Diagnostic interpretation matrix (why this tool exists)
| Observation from the Diagnozer | Most likely problem location |
|--------------------------------|------------------------------|
| Clean reads, low RTT, all GOOD — while SCADA still complains | SCADA host itself: per-machine DCOM permissions, CPU/memory saturation, its own group/subscription load |
| Diagnozer also sees disconnects / RPC errors | Shared path: network, firewall, DCOM layer, or OPC server host |
| Connection stable, but `BAD_COMM_FAILURE` on many device tags | Link between the OPC server and the control devices (downstream of OPC) — **not** a DCOM/network problem |
| Slow RTT spikes at consistent times of day | Server load pattern; correlate with heartbeat summaries |
| Hangs without errors returned (D7) | Silent network drop (firewall/MTU/NIC) — classic DCOM pitfall |
| One instance (SCADA zone) slow, other (server zone) fast | Network segment between the zones |
## 13. Acceptance criteria (v1.0)
- **AC1** Runs as a service, survives reboot, auto-starts, recovers from a killed process.
- **AC2** Detects OPC server process stop within one poll interval (or one hang window for
silent drops).
- **AC3** Detects injected latency above thresholds within 1–2 polls; event contains
measured RTT.
- **AC4** Quality transitions produce events with raw code and decoded name.
- **AC5** Staleness/freeze detection within tolerance of `max_age_s`.
- **AC6** No OPC writes are ever issued (code review + no write path exists).
- **AC7** Events land in JSONL and Event Log; heartbeats appear even when all is healthy.
- **AC8** Invalid config fails fast with actionable messages.
- **AC9** Footprint ≤ ~50 MB RAM, ~0% CPU while idle-polling on a healthy link.
- **AC10** 24 h soak against a simulation server: no leaks, correct reconnect accounting.
## 14. Future extensions (post-v1)
- Async subscription monitoring (`IOPCAsyncIO2` DataChange) to compare push vs. poll
latency — validates the SCADA's actual callback path.
- Per-item latency bisection (read items individually to isolate a slow tag).
- SQLite time-series of samples for post-incident graphing.
- Prometheus exporter / Grafana dashboard.
- Email / Teams / webhook alerting with deduplication.
- Multi-server monitoring in one service.