# \# AquaCom Integration Gateway – Architecture
#
# \## 1. Purpose
#
# This document defines the high-level software architecture of the \*\*AquaCom Integration Gateway\*\*.
#
# It describes:
#
# \- major system components;
# \- dependency direction;
# \- data flows;
# \- architectural boundaries;
# \- live-data handling;
# \- historical-data handling;
# \- OPC UA integration;
# \- storage integration;
# \- diagnostics;
# \- security boundaries;
# \- extension points.
#
# Detailed functional requirements are defined in:
#
# ```text
# docs/product/software-specification.md
# ```
#
# Implementation requirements and Codex-specific development rules are defined in:
#
# ```text
# docs/product/codex-implementation-specification.md
# AGENTS.md
# ```
#
# Detailed subsystem architecture is documented under:
#
# ```text
# docs/architecture/
# ```
#
# AquaCom-specific protocol knowledge is documented under:
#
# ```text
# docs/protocol/
# ```
#
# \---
#
# \# 2. System purpose
#
# The AquaCom Integration Gateway provides a modern integration boundary between AquaCom-compatible field equipment and higher-level systems.
#
# The gateway shall:
#
# \- communicate with AquaCom field devices;
# \- acquire current process values;
# \- retrieve historical process values;
# \- normalize AquaCom-specific information into a protocol-independent model;
# \- expose current values using OPC UA;
# \- expose historical values using OPC UA Historical Access;
# \- store historical data in one or more configurable destinations;
# \- recover historical information following communication interruptions;
# \- provide operational and protocol diagnostics.
#
# The gateway shall not make higher-level systems dependent on AquaCom-specific behavior.
#
# \---
#
# \# 3. Architectural principle
#
# The central architecture is:
#
# ```text
# AquaCom field device
#   │
#   ▼
# AquaCom Transport
#   │
#   ▼
# AquaCom Protocol Engine
#   │
#   ▼
# Station / Session Manager
#   │
#   ▼
# Canonical Data Model
#   │
#   ├─────────────────────► Current-State Service
#   │ │
#   │ ▼
#   │ OPC UA Data Access
#   │
#   └─────────────────────► Historical Pipeline
#   │
#   ┌───────────┼────────────┐
#   │ │ │
#   ▼ ▼ ▼
#   Repository Storage A Storage B
#   │
#   ▼
#   OPC UA Historical Access
# ```
#
# The canonical data model forms the boundary between AquaCom-specific functionality and all northbound integrations.
#
# \---
#
# \# 4. Architectural goals
#
# The architecture shall support:
#
# \- protocol isolation;
# \- storage independence;
# \- stable internal identifiers;
# \- stable OPC UA NodeIds;
# \- correct handling of source timestamps;
# \- reliable history recovery;
# \- multiple historical storage destinations;
# \- store-and-forward;
# \- independent subsystem testing;
# \- restart recovery;
# \- future replacement of individual technologies;
# \- future addition of other northbound interfaces.
#
# The architecture shall avoid tight coupling between:
#
# ```text
# AquaCom
# OPC UA
# Database technology
# Historian technology
# SCADA platform
# ```
#
# \---
#
# \# 5. Architectural boundaries
#
# The following boundaries are mandatory.
#
# \## 5.1 AquaCom boundary
#
# Only the AquaCom subsystem may:
#
# \- encode AquaCom telegrams;
# \- decode AquaCom telegrams;
# \- calculate or verify AquaCom checksums;
# \- interpret AquaCom operation codes;
# \- interpret AquaCom addressing;
# \- interpret AquaCom-specific value formats.
#
# No OPC UA or storage module shall perform AquaCom protocol processing.
#
# \---
#
# \## 5.2 Canonical model boundary
#
# AquaCom data shall be converted into canonical gateway objects before being forwarded to:
#
# \- current-state handling;
# \- history handling;
# \- OPC UA;
# \- storage systems;
# \- diagnostics where appropriate.
#
# The canonical model shall remain independent of AquaCom and OPC UA.
#
# \---
#
# \## 5.3 OPC UA boundary
#
# The OPC UA subsystem shall consume canonical gateway information.
#
# It shall not:
#
# \- communicate directly with AquaCom stations;
# \- decode telegrams;
# \- synchronously request historical data from an RTU;
# \- depend upon a particular storage technology.
#
# \---
#
# \## 5.4 Storage boundary
#
# Storage destinations shall receive canonical historical records.
#
# Storage implementations shall not depend upon:
#
# \- AquaCom telegrams;
# \- AquaCom transport;
# \- OPC UA server internals.
#
# \---
#
# \# 6. Source tree
#
# The logical source structure is:
#
# ```text
# src/
# ├── core/
# ├── aquacom/
# ├── history/
# ├── storage/
# ├── opcua/
# ├── diagnostics/
# └── host/
# ```
#
# The exact language-specific package or project structure may differ, but the architectural responsibilities shall remain equivalent.
#
# \---
#
# \# 7. Dependency direction
#
# Allowed dependencies shall broadly follow:
#
# ```text
#   host
#   │
#   ┌───────────┼─────────────┐
#   │ │ │
#   ▼ ▼ ▼
#   opcua history diagnostics
#   │ │
#   │ storage
#   │ │
#   └──────┬────┘
#   ▼
#   core
#   ▲
#   │
#   aquacom
# ```
#
# The most important rule is:
#
# ```text
# core
# ```
#
# shall not depend upon:
#
# ```text
# aquacom
# opcua
# storage technology
# ```
#
# \---
#
# \# 8. Core subsystem
#
# The `core` subsystem contains protocol-independent domain concepts.
#
# Examples include:
#
# ```text
# StationId
# PointId
# CurrentValue
# HistoricalSample
# DataQuality
# AcquisitionSource
# CommunicationState
# StationState
# HistorySynchronizationState
# ```
#
# The core subsystem defines shared contracts used between other modules.
#
# It shall contain no AquaCom protocol logic.
#
# It shall contain no OPC UA-specific types.
#
# It shall contain no database-specific types.
#
# \---
#
# \# 9. AquaCom subsystem
#
# The AquaCom subsystem contains:
#
# ```text
# Transport
# Protocol codec
# Telegram validation
# Station/session handling
# Live acquisition
# Historical acquisition
# Protocol diagnostics
# ```
#
# Logical structure:
#
# ```text
# AquaCom Transport
#   │
#   ▼
# Protocol Codec
#   │
#   ▼
# Protocol Operations
#   │
#   ▼
# Station Session
#   │
#   ├── Live Acquisition
#   └── Historical Acquisition
# ```
#
# Protocol implementation shall be evidence-based.
#
# Undocumented AquaCom behavior shall not be guessed.
#
# \---
#
# \# 10. AquaCom transport
#
# The transport layer is responsible for communication only.
#
# It may support implementations such as:
#
# ```text
# TCP
# Serial
# Serial-over-IP
# Other supported AquaCom transport
# ```
#
# The transport layer shall not interpret process values.
#
# Conceptual interface:
#
# ```text
# open
# close
# send
# receive
# health
# ```
#
# \---
#
# \# 11. AquaCom protocol engine
#
# The protocol engine is responsible for:
#
# \- framing;
# \- telegram validation;
# \- checksum handling;
# \- request encoding;
# \- response decoding;
# \- protocol error interpretation.
#
# Conceptual transformation:
#
# ```text
# raw bytes
#   │
#   ▼
# AquaCom message
#   │
#   ▼
# logical protocol result
# ```
#
# The codec shall be independently testable without a physical AquaCom device.
#
# \---
#
# \# 12. Station/session manager
#
# Each AquaCom station has an independent logical session.
#
# Conceptual station states:
#
# ```text
# DISABLED
# INITIALIZING
# CONNECTING
# ONLINE
# DEGRADED
# OFFLINE
# RECOVERING
# ```
#
# One failing station shall not stop communication with unrelated stations.
#
# The Station Manager owns:
#
# \- station lifecycle;
# \- communication status;
# \- retries;
# \- scheduling;
# \- station diagnostics;
# \- history recovery coordination.
#
# \---
#
# \# 13. Canonical data model
#
# The gateway uses a protocol-independent canonical model.
#
# \## 13.1 CurrentValue
#
# Conceptually:
#
# ```text
# CurrentValue
#   StationId
#   PointId
#   Value
#   DataType
#   Quality
#   SourceTimestamp
#   ReceivedTimestamp
#   UpdatedTimestamp
#   AcquisitionSource
# ```
#
# \---
#
# \## 13.2 HistoricalSample
#
# Conceptually:
#
# ```text
# HistoricalSample
#   StationId
#   PointId
#   Value
#   DataType
#   Quality
#   SourceTimestamp
#   ReceivedTimestamp
#   AcquisitionSource
#   AcquisitionId
# ```
#
# Historical samples shall retain the timestamp associated with the process state.
#
# \---
#
# \# 14. Timestamp model
#
# The gateway shall distinguish at least:
#
# ```text
# SourceTimestamp
# ReceivedTimestamp
# ```
#
# Where applicable also:
#
# ```text
# UpdatedTimestamp
# ServerTimestamp
# ```
#
# Their meanings are:
#
# | Timestamp | Meaning |
# |---|---|
# | SourceTimestamp | Time associated with the value at the source |
# | ReceivedTimestamp | Time the gateway received the information |
# | UpdatedTimestamp | Time current gateway state was changed |
# | ServerTimestamp | Timestamp used by the OPC UA server |
#
# The following must never be assumed:
#
# ```text
# ReceivedTimestamp = SourceTimestamp
# ```
#
# \---
#
# \# 15. Fundamental historical rule
#
# The fundamental historical-data rule is:
#
# > A historical sample represents the process at its SourceTimestamp, not at the time the gateway receives the sample.
#
# Example:
#
# ```text
# Historical value:
#   SourceTimestamp = 14:05
#   ReceivedTimestamp = 18:30
# ```
#
# The value belongs to history at:
#
# ```text
# 14:05
# ```
#
# It shall not become a new current process value at:
#
# ```text
# 18:30
# ```
#
# \---
#
# \# 16. Live-data architecture
#
# Live AquaCom values follow:
#
# ```text
# AquaCom response
#   │
#   ▼
# Protocol decode
#   │
#   ▼
# Point mapping
#   │
#   ▼
# Canonical CurrentValue
#   │
#   ▼
# Current-State Service
#   │
#   ├────────► OPC UA
#   │
#   └────────► Historical pipeline
#   if live historization is enabled
# ```
#
# The Current-State Service maintains the latest accepted value for each configured point.
#
# \---
#
# \# 17. Current-State Service
#
# Responsibilities:
#
# \- maintain the latest current value;
# \- reject obsolete current-state updates where applicable;
# \- expose current values to OPC UA;
# \- notify subscribers of valid changes;
# \- preserve quality and timestamps.
#
# Conceptual interface:
#
# ```text
# update(CurrentValue)
#
# get(PointId)
#
# getAll(StationId)
#
# subscribe(PointId)
# ```
#
# Historical backfill shall not directly call `update(CurrentValue)`.
#
# \---
#
# \# 18. Historical-data architecture
#
# Historical AquaCom data follows:
#
# ```text
# AquaCom history
#   │
#   ▼
# Historical Acquisition Manager
#   │
#   ▼
# Canonical HistoricalSample
#   │
#   ▼
# Historical Pipeline
#   │
#   ├────────► History Repository
#   ├────────► Storage Sink A
#   ├────────► Storage Sink B
#   └────────► Other configured destinations
# ```
#
# The historical pipeline is independent from OPC UA.
#
# \---
#
# \# 19. Historical Acquisition Manager
#
# The Historical Acquisition Manager is responsible for:
#
# \- determining missing intervals;
# \- requesting AquaCom history;
# \- processing historical responses;
# \- maintaining synchronization state;
# \- managing watermarks;
# \- performing reconnect/backfill;
# \- throttling history retrieval;
# \- avoiding interference with live polling.
#
# Live acquisition shall normally have higher communication priority than bulk history recovery.
#
# \---
#
# \# 20. Historical synchronization
#
# Each station may maintain persistent synchronization state.
#
# Conceptually:
#
# ```text
# StationId
# HistoryStreamId
# LastCompleteTimestamp
# LastAttemptTimestamp
# LastSuccessfulTimestamp
# SynchronizationState
# ```
#
# Example:
#
# ```text
# 12:00 history synchronized
#
# 12:03 communication lost
#
# 17:24 communication restored
#
# 12:00 → 17:24
#   identified as recovery interval
# ```
#
# The gateway then retrieves available AquaCom history for that interval.
#
# \---
#
# \# 21. Watermark rule
#
# A history synchronization watermark shall only advance after the corresponding interval has been successfully handled according to the configured persistence policy.
#
# The following is prohibited:
#
# ```text
# receive historical packet
#   │
#   ▼
# advance watermark
#   │
#   ▼
# storage fails
# ```
#
# Preferred behavior is:
#
# ```text
# receive
#   ↓
# validate
#   ↓
# persist/durably queue
#   ↓
# advance synchronization state
# ```
#
# \---
#
# \# 22. Historical pipeline
#
# The historical pipeline shall conceptually perform:
#
# ```text
# HistoricalSample
#   │
#   ▼
# Validation
#   │
#   ▼
# Normalization
#   │
#   ▼
# Deduplication
#   │
#   ▼
# Durable Spool
#   │
#   ▼
# Distribution
# ```
#
# This pipeline provides a stable boundary between acquisition and storage.
#
# \---
#
# \# 23. Deduplication
#
# The default historical logical identity is:
#
# ```text
# StationId
# \+
# PointId
# \+
# SourceTimestamp
# ```
#
# A stronger AquaCom-provided identifier may be used where verified.
#
# Identical samples shall not create unintended duplicate history.
#
# Conflicting samples sharing the same logical identity shall generate diagnostics.
#
# The default conflict strategy should favor explicit conflict detection rather than silent overwrite.
#
# \---
#
# \# 24. Durable spool
#
# The historical spool provides restart-safe delivery.
#
# Conceptually:
#
# ```text
# HistoricalSample
#   │
#   ▼
# Persistent spool
#   │
#   ├────► Repository
#   ├────► Sink A
#   └────► Sink B
# ```
#
# Each destination maintains independent acknowledgement.
#
# Example:
#
# ```text
# Record 4711
#
# Repository ACK
# CentralHistorian ACK
# Archive PENDING
# ```
#
# The record remains until configured delivery requirements have been fulfilled.
#
# \---
#
# \# 25. History Repository
#
# A History Repository is a queryable historical source.
#
# It provides operations conceptually equivalent to:
#
# ```text
# store
# storeBatch
# readRaw
# readAtTime
# getBounds
# health
# ```
#
# The repository used by OPC UA Historical Access is selected by configuration.
#
# The OPC UA implementation shall not know whether the repository is:
#
# ```text
# relational database
# time-series database
# embedded historian
# industrial historian
# other queryable implementation
# ```
#
# \---
#
# \# 26. Storage Sink
#
# A Storage Sink is a destination receiving historical records.
#
# Conceptual interface:
#
# ```text
# initialize
# write
# writeBatch
# flush
# health
# shutdown
# ```
#
# A sink does not need to support historical queries.
#
# Examples:
#
# ```text
# SQL database
# time-series database
# enterprise historian
# file archive
# message broker
# data lake connector
# ```
#
# \---
#
# \# 27. Repository versus sink
#
# These shall remain separate concepts:
#
# ```text
# Repository
#   = query historical data
#
# Sink
#   = receive historical data
# ```
#
# One implementation may support both.
#
# Example:
#
# ```text
# Local historian
#   Repository: yes
#   Sink: yes
#
# Archive export
#   Repository: no
#   Sink: yes
# ```
#
# \---
#
# \# 28. Multiple storage destinations
#
# A historical record may be delivered to multiple independent destinations.
#
# Example:
#
# ```text
#   Historical Pipeline
#   │
#   ┌───────────────┼────────────────┐
#   │ │ │
#   ▼ ▼ ▼
#   Local Repository Central DB Archive
# ```
#
# Failure of one destination shall not unnecessarily block successful destinations.
#
# \---
#
# \# 29. OPC UA architecture
#
# The OPC UA subsystem provides northbound access to normalized gateway information.
#
# Logical components:
#
# ```text
# OPC UA Server
#   │
#   ├── Namespace Manager
#   ├── Current Value Provider
#   ├── Historical Provider
#   ├── Quality Mapper
#   ├── Diagnostics Provider
#   └── Security
# ```
#
# \---
#
# \# 30. OPC UA current data
#
# Current values are exposed through normal OPC UA Data Access.
#
# Mapping:
#
# ```text
# CurrentValue.Value
#   ↓
# OPC UA Value
#
# CurrentValue.SourceTimestamp
#   ↓
# OPC UA SourceTimestamp
#
# Gateway server time
#   ↓
# OPC UA ServerTimestamp
#
# CurrentValue.Quality
#   ↓
# OPC UA StatusCode
# ```
#
# \---
#
# \# 31. OPC UA Historical Access
#
# Historical Access shall query the configured History Repository.
#
# Correct flow:
#
# ```text
# OPC UA Client
#   │
#   │ HistoryRead
#   ▼
# OPC UA Server
#   │
#   ▼
# Historical Provider
#   │
#   ▼
# History Repository
#   │
#   ▼
# HistoricalSample\[]
#   │
#   ▼
# OPC UA DataValue\[]
# ```
#
# \---
#
# \# 32. Prohibited HistoryRead architecture
#
# The following architecture is prohibited:
#
# ```text
# OPC UA HistoryRead
#   │
#   ▼
# AquaCom request
#   │
#   ▼
# wait for RTU
#   │
#   ▼
# OPC UA response
# ```
#
# Historical synchronization and historical client access must be decoupled.
#
# \---
#
# \# 33. OPC UA namespace
#
# The default logical namespace shall resemble:
#
# ```text
# AquaCom
# │
# ├── Gateway
# │ ├── Status
# │ ├── Version
# │ ├── StartTime
# │ ├── ConfigurationVersion
# │ ├── HistoricalQueueDepth
# │ └── Storage
# │
# └── Stations
#   │
#   ├── PS001
#   │ ├── Process
#   │ │ ├── Level
#   │ │ ├── Pump01Running
#   │ │ └── Pump02Running
#   │ │
#   │ └── Diagnostics
#   │ ├── CommunicationState
#   │ ├── LastCommunication
#   │ ├── HistoryState
#   │ └── HistoryWatermark
#   │
#   └── PS002
# ```
#
# Exact organization may be configurable.
#
# \---
#
# \# 34. Stable OPC UA NodeIds
#
# OPC UA NodeIds shall derive from stable engineering identifiers.
#
# Example:
#
# ```text
# station/PS001/point/LEVEL
# ```
#
# Changing:
#
# ```text
# Wet well level
# ```
#
# to:
#
# ```text
# Inlet sump level
# ```
#
# shall not normally change the NodeId.
#
# Stable NodeIds are required to preserve client configuration.
#
# \---
#
# \# 35. Diagnostics architecture
#
# Diagnostics are separate from process data.
#
# Conceptually:
#
# ```text
# Diagnostics
# │
# ├── Gateway
# │
# ├── Station
# │
# ├── AquaCom Protocol
# │
# ├── History
# │
# ├── Storage
# └── OPC UA
# ```
#
# Diagnostics may be exposed through:
#
# \- logs;
# \- metrics;
# \- OPC UA diagnostic nodes;
# \- future management interfaces.
#
# \---
#
# \# 36. Gateway diagnostics
#
# Examples:
#
# ```text
# GatewayState
# Version
# ConfigurationVersion
# StartTime
# Uptime
# StationCount
# OnlineStationCount
# HistoricalQueueDepth
# SpoolDiskUsage
# OPCUAState
# ```
#
# \---
#
# \# 37. Station diagnostics
#
# Examples:
#
# ```text
# CommunicationState
# LastRequest
# LastResponse
# LastSuccessfulCommunication
# ConsecutiveFailures
# ProtocolErrors
# HistorySynchronizationState
# HistoryWatermark
# HistoricalBacklog
# ```
#
# \---
#
# \# 38. Storage diagnostics
#
# Per destination:
#
# ```text
# State
# LastSuccessfulWrite
# LastFailure
# PendingRecords
# RetryCount
# Latency
# ```
#
# A storage failure shall be identifiable independently from an AquaCom communication failure.
#
# \---
#
# \# 39. Logging
#
# Structured logging is preferred.
#
# Useful context includes:
#
# ```text
# timestamp
# severity
# component
# stationId
# pointId
# operation
# correlationId
# message
# error
# ```
#
# Raw AquaCom telegram logging shall be separately configurable.
#
# \---
#
# \# 40. Configuration architecture
#
# Configuration shall be external and machine-readable.
#
# Conceptual structure:
#
# ```text
# Gateway Configuration
# │
# ├── Gateway
# ├── AquaCom
# ├── Stations
# ├── Points
# ├── History
# ├── Storage
# ├── OPC UA
# ├── Security
# ├── Diagnostics
# └── Logging
# ```
#
# Configuration validation occurs before activation.
#
# \---
#
# \# 41. Station configuration
#
# A station definition contains concepts equivalent to:
#
# ```text
# StationId
# Enabled
# Transport
# AquaComAddress
# ProtocolProfile
# LiveAcquisition
# HistoricalAcquisition
# PointDefinitionSource
# Timezone
# ```
#
# Station configuration shall not be embedded directly in protocol source code.
#
# \---
#
# \# 42. Point configuration
#
# A point contains concepts equivalent to:
#
# ```text
# PointId
# DisplayName
# Description
# SourceReference
# DataType
# EngineeringUnit
# Scaling
# LiveEnabled
# HistoryEnabled
# OPCUAEnabled
# Historizing
# StoragePolicy
# ```
#
# `PointId` shall remain stable even if presentation metadata changes.
#
# \---
#
# \# 43. Security boundaries
#
# The architecture assumes AquaCom is a legacy field protocol.
#
# Security shall therefore be applied around the AquaCom communication environment.
#
# Conceptually:
#
# ```text
# SCADA / client network
#   │
#   ▼
# Firewall / segmentation
#   │
#   ▼
# AquaCom Gateway
#   │
#   ▼
# OT communication network
#   │
#   ▼
# Site firewall/router/VPN
#   │
#   ▼
# AquaCom RTU
# ```
#
# The gateway shall not assume that AquaCom itself provides modern confidentiality, authentication or authorization.
#
# \---
#
# \# 44. OPC UA security
#
# OPC UA security is handled within the OPC UA subsystem.
#
# Production architecture shall support:
#
# ```text
# application certificates
# trusted client management
# secure channels
# authentication
# authorization
# encrypted communication
# ```
#
# Insecure endpoints shall not be the normal production default.
#
# \---
#
# \# 45. Secrets boundary
#
# Secrets shall not form part of normal version-controlled configuration.
#
# Examples:
#
# ```text
# database passwords
# API tokens
# private keys
# certificate private keys
# ```
#
# These shall be injected through an external secret mechanism.
#
# \---
#
# \# 46. Host subsystem
#
# The `host` subsystem composes the application.
#
# Responsibilities include:
#
# \- configuration loading;
# \- dependency construction;
# \- subsystem startup;
# \- lifecycle management;
# \- shutdown;
# \- top-level health state.
#
# The host shall not become a location for protocol or business logic.
#
# \---
#
# \# 47. Startup architecture
#
# Conceptual startup sequence:
#
# ```text
# Load configuration
#   │
#   ▼
# Validate configuration
#   │
#   ▼
# Load persistent state
#   │
#   ▼
# Initialize storage
#   │
#   ▼
# Initialize historical services
#   │
#   ▼
# Initialize OPC UA
#   │
#   ▼
# Initialize AquaCom stations
#   │
#   ▼
# Start live acquisition
#   │
#   ▼
# Start historical synchronization
# ```
#
# A temporary failure of a non-critical secondary storage destination should not necessarily prevent the gateway from starting.
#
# \---
#
# \# 48. Shutdown architecture
#
# Conceptual controlled shutdown:
#
# ```text
# Stop accepting administrative changes
#   │
#   ▼
# Stop scheduling new acquisition
#   │
#   ▼
# Complete/cancel active transactions safely
#   │
#   ▼
# Persist synchronization state
#   │
#   ▼
# Flush durable state
#   │
#   ▼
# Stop OPC UA
#   │
#   ▼
# Close storage
#   │
#   ▼
# Terminate
# ```
#
# \---
#
# \# 49. Restart recovery
#
# After an unclean restart:
#
# ```text
# Load configuration
#   │
#   ▼
# Recover persistent spool
#   │
#   ▼
# Restore synchronization watermarks
#   │
#   ▼
# Reconnect AquaCom stations
#   │
#   ▼
# Resume live acquisition
#   │
#   ▼
# Resume historical recovery
# ```
#
# Live acquisition should resume before large backlog processing.
#
# \---
#
# \# 50. Scheduling priorities
#
# Where AquaCom communication capacity is limited, scheduling shall conceptually prioritize:
#
# ```text
# 1\. communication/session health
# 2\. current/live acquisition
# 3\. alarms/events when implemented
# 4\. explicit configuration operations
# 5\. historical backfill
# 6\. low-priority maintenance
# ```
#
# Historical synchronization shall be throttleable.
#
# \---
#
# \# 51. Resource boundaries
#
# All queues and caches shall be bounded.
#
# This applies to:
#
# ```text
# AquaCom request queues
# history queues
# storage retry queues
# OPC UA historical result sets
# continuation state
# logging buffers
# spool storage
# ```
#
# Overflow behavior shall be explicit and observable.
#
# \---
#
# \# 52. Testing architecture
#
# The system shall support independent testing of each architectural boundary.
#
# Conceptually:
#
# ```text
# Protocol Fixtures
#   │
#   ▼
# AquaCom Codec Tests
#
# Simulator
#   │
#   ▼
# Session / Acquisition Tests
#
# Historical Fixtures
#   │
#   ▼
# History Pipeline Tests
#
# Repository
#   │
#   ▼
# OPC UA HA Tests
#
# Current-State Service
#   │
#   ▼
# OPC UA DA Tests
# ```
#
# \---
#
# \# 53. AquaCom simulator
#
# The simulator shall permit development without operational AquaCom equipment.
#
# Supported scenarios shall eventually include:
#
# ```text
# normal live values
# normal history
# timeouts
# disconnects
# delayed response
# malformed telegram
# bad checksum
# duplicate history
# conflicting history
# clock error
# reconnect
# backfill
# ```
#
# The simulator is part of the architecture, not merely a temporary development tool.
#
# \---
#
# \# 54. Protocol evidence architecture
#
# AquaCom implementation is linked to documented evidence.
#
# Relevant repository area:
#
# ```text
# docs/protocol/
# ```
#
# Recommended structure:
#
# ```text
# aquacom.md
# known-operations.md
# protocol-gaps.md
# test-vectors.md
# ```
#
# Every implemented AquaCom behavior should be traceable to:
#
# ```text
# Specification
# Capture
# Known-good implementation
# Approved test vector
# ```
#
# Unknown behavior remains explicitly unresolved.
#
# \---
#
# \# 55. Error isolation
#
# Failures shall remain contained where possible.
#
# Examples:
#
# | Failure | Expected isolation |
# |---|---|
# | Station A offline | Station B continues |
# | Storage A offline | Storage B continues |
# | OPC UA client disconnect | Acquisition continues |
# | OPC UA server problem | AquaCom acquisition should continue where possible |
# | Historical backfill fails | Live acquisition continues |
# | Malformed AquaCom telegram | Telegram rejected, station diagnostics updated |
# | Secondary storage failure | Durable spool retains pending delivery |
#
# \---
#
# \# 56. Future extension points
#
# The architecture shall permit future addition of:
#
# ```text
# OPC UA Alarms \& Conditions
# AquaCom alarms/events
# AquaCom commands
# setpoint changes
# MQTT
# REST API
# external analytics
# central configuration
# redundant gateways
# high availability
# additional history repositories
# additional storage sinks
# ```
#
# These shall be added behind explicit subsystem interfaces.
#
# \---
#
# \# 57. Future process-control architecture
#
# If control functionality is introduced later, it shall use a separate command pipeline:
#
# ```text
# Northbound request
#   │
#   ▼
# Authentication
#   │
#   ▼
# Authorization
#   │
#   ▼
# Command validation
#   │
#   ▼
# Command service
#   │
#   ▼
# AquaCom command
#   │
#   ▼
# Confirmation / readback
#   │
#   ▼
# Audit
# ```
#
# A direct mapping from arbitrary OPC UA writes to raw AquaCom telegrams is not an acceptable control architecture.
#
# \---
#
# \# 58. Architectural invariants
#
# The following invariants shall hold throughout implementation.
#
# \## INV-001
#
# AquaCom-specific logic exists only behind the AquaCom abstraction.
#
# \## INV-002
#
# The canonical model contains no AquaCom telegram representation.
#
# \## INV-003
#
# The canonical model contains no OPC UA-specific representation.
#
# \## INV-004
#
# Historical samples do not update current state solely because they were recently retrieved.
#
# \## INV-005
#
# Historical SourceTimestamp is preserved.
#
# \## INV-006
#
# OPC UA HistoryRead queries a repository, not an AquaCom device.
#
# \## INV-007
#
# A storage failure does not directly stop unrelated live AquaCom acquisition.
#
# \## INV-008
#
# Point identity remains stable across display-name changes.
#
# \## INV-009
#
# OPC UA NodeIds remain stable across restart and normal upgrades.
#
# \## INV-010
#
# Unverified AquaCom protocol details are not implemented as guesses.
#
# \## INV-011
#
# Synchronization state required for recovery is persistent.
#
# \## INV-012
#
# Historical delivery supports bounded persistent buffering.
#
# \---
#
# \# 59. Primary end-to-end data flows
#
# \## 59.1 Live data
#
# ```text
# AquaCom RTU
#   │
#   ▼
# Transport
#   │
#   ▼
# Protocol Engine
#   │
#   ▼
# Station Manager
#   │
#   ▼
# CurrentValue
#   │
#   ▼
# Current-State Service
#   │
#   ├────► OPC UA
#   │
#   └────► Historical Pipeline
#   when live historization is enabled
# ```
#
# \---
#
# \## 59.2 AquaCom historical recovery
#
# ```text
# AquaCom RTU
#   │
#   ▼
# Historical Acquisition
#   │
#   ▼
# HistoricalSample
#   │
#   ▼
# Validation
#   │
#   ▼
# Deduplication
#   │
#   ▼
# Durable Spool
#   │
#   ├────► Repository
#   ├────► Storage A
#   └────► Storage B
# ```
#
# \---
#
# \## 59.3 OPC UA historical request
#
# ```text
# OPC UA Client
#   │
#   ▼
# HistoryRead
#   │
#   ▼
# OPC UA Historical Provider
#   │
#   ▼
# History Repository
#   │
#   ▼
# HistoricalSample\[]
#   │
#   ▼
# OPC UA DataValue\[]
# ```
#
# \---
#
# \# 60. Reference architecture
#
# The complete reference architecture is:
#
# ```text
#   FIELD / AQUACOM
#   │
#   ▼
#   ┌─────────────────────┐
#   │ AquaCom Transport │
#   └──────────┬──────────┘
#   │
#   ▼
#   ┌─────────────────────┐
#   │ Protocol Engine │
#   └──────────┬──────────┘
#   │
#   ▼
#   ┌─────────────────────┐
#   │ Station Manager │
#   └──────────┬──────────┘
#   │
#   ▼
#   ┌─────────────────────┐
#   │ Canonical Model │
#   └───────┬───────┬─────┘
#   │ │
#   LIVE HISTORY
#   │ │
#   ▼ ▼
#   ┌──────────────┐ ┌──────────────────┐
#   │Current-State │ │Historical │
#   │Service │ │Acquisition │
#   └──────┬───────┘ └────────┬─────────┘
#   │ │
#   │ ▼
#   │ ┌──────────────────┐
#   │ │Historical │
#   │ │Pipeline │
#   │ └────────┬─────────┘
#   │ │
#   │ ┌──────────┼───────────┐
#   │ │ │ │
#   │ ▼ ▼ ▼
#   │ Repository Sink A Sink B
#   │ │
#   │ │
#   ▼ ▼
#   ┌────────────────────────────┐
#   │ OPC UA Server │
#   │ │
#   │ Data Access │
#   │ Historical Access │
#   │ Diagnostics │
#   └──────────────┬─────────────┘
#   │
#   ▼
#   SCADA / Clients
# ```
#
# \---
#
# \# 61. Architecture decision summary
#
# The gateway is intentionally designed as an:
#
# ```text
# AquaCom Integration Gateway
# ```
#
# rather than merely an:
#
# ```text
# AquaCom OPC UA Server
# ```
#
# This allows:
#
# \- OPC UA to be replaced or supplemented;
# \- storage technology to change;
# \- multiple historians to coexist;
# \- AquaCom equipment to be gradually retired;
# \- other northbound interfaces to be added;
# \- historical acquisition to continue independently of OPC UA clients.
#
# The long-term architectural asset is therefore the normalized integration layer and historical recovery mechanism, not any single external interface.
#
# \---
#
# \# 62. Final architectural rule
#
# The most important data rule is:
#
# > Historical data is stored and exposed according to when the process value was valid, not when the gateway happened to retrieve it.
#
# The most important protocol rule is:
#
# > AquaCom behavior must be based on verified protocol knowledge and must never be invented merely to complete an implementation.
#
# The most important software rule is:
#
# > AquaCom, canonical data handling, historical persistence and OPC UA shall remain separate architectural concerns.