37 KiB
AquaCom Integration Gateway – Architecture
1. Purpose
This document defines the high-level software architecture of the AquaCom Integration Gateway.
It describes:
-
major system components;
-
dependency direction;
-
data flows;
-
architectural boundaries;
-
live-data handling;
-
historical-data handling;
-
OPC UA integration;
-
storage integration;
-
diagnostics;
-
security boundaries;
-
extension points.
Detailed functional requirements are defined in:
docs/product/software-specification.md
Implementation requirements and Codex-specific development rules are defined in:
docs/product/codex-implementation-specification.md
AGENTS.md
Document roles and precedence. When documents overlap or conflict, the following precedence applies:
docs/product/software-specification.md— the authoritative statement of what the gateway shall do (requirements).- This document — the authoritative statement of how the system is structured to meet those requirements (architecture, boundaries, interfaces).
docs/product/codex-implementation-specification.md— the authoritative statement of how implementation work proceeds (phases, task sizing, test strategy, completion criteria). It restates architectural rules for implementer convenience but does not redefine them.docs/configuration/configuration-reference.md— the authoritative reference for configuration semantics (field names, defaults, validation rules).AGENTS.md— the entry-point summary for coding agents; it points to the documents above and never overrides them.
A data contract or interface is defined once in the authoritative document for its role; other documents link to it rather than restating it with different names. Where a contract is currently restated (for historical reasons), the definition in the role-authoritative document wins.
Detailed subsystem architecture is documented under:
docs/architecture/
AquaCom-specific protocol knowledge is documented under:
docs/protocol/
2. System purpose
The AquaCom Integration Gateway provides a modern integration boundary between AquaCom-compatible field equipment and higher-level systems.
The gateway shall:
-
communicate with AquaCom field devices;
-
acquire current process values;
-
retrieve historical process values;
-
normalize AquaCom-specific information into a protocol-independent model;
-
expose current values using OPC UA;
-
expose historical values using OPC UA Historical Access;
-
store historical data in one or more configurable destinations;
-
recover historical information following communication interruptions;
-
provide operational and protocol diagnostics.
The gateway shall not make higher-level systems dependent on AquaCom-specific behavior.
3. Architectural principle
The central architecture is:
AquaCom field device
│
▼
AquaCom Transport
│
▼
AquaCom Protocol Engine
│
▼
Station / Session Manager
│
▼
Canonical Data Model
│
├─────────────────────► Current-State Service
│ │
│ ▼
│ OPC UA Data Access
│
└─────────────────────► Historical Pipeline
│
┌───────────┼────────────┐
│ │ │
▼ ▼ ▼
Repository Storage A Storage B
│
▼
OPC UA Historical Access
The canonical data model forms the boundary between AquaCom-specific functionality and all northbound integrations.
4. Architectural goals
The architecture shall support:
-
protocol isolation;
-
storage independence;
-
stable internal identifiers;
-
stable OPC UA NodeIds;
-
correct handling of source timestamps;
-
reliable history recovery;
-
multiple historical storage destinations;
-
store-and-forward;
-
independent subsystem testing;
-
restart recovery;
-
future replacement of individual technologies;
-
future addition of other northbound interfaces.
The architecture shall avoid tight coupling between:
AquaCom
OPC UA
Database technology
Historian technology
SCADA platform
5. Architectural boundaries
The following boundaries are mandatory.
5.1 AquaCom boundary
Only the AquaCom subsystem may:
-
encode AquaCom telegrams;
-
decode AquaCom telegrams;
-
calculate or verify AquaCom checksums;
-
interpret AquaCom operation codes;
-
interpret AquaCom addressing;
-
interpret AquaCom-specific value formats.
No OPC UA or storage module shall perform AquaCom protocol processing.
5.2 Canonical model boundary
AquaCom data shall be converted into canonical gateway objects before being forwarded to:
-
current-state handling;
-
history handling;
-
OPC UA;
-
storage systems;
-
diagnostics where appropriate.
The canonical model shall remain independent of AquaCom and OPC UA.
5.3 OPC UA boundary
The OPC UA subsystem shall consume canonical gateway information.
It shall not:
-
communicate directly with AquaCom stations;
-
decode telegrams;
-
synchronously request historical data from an RTU;
-
depend upon a particular storage technology.
5.4 Storage boundary
Storage destinations shall receive canonical historical records.
Storage implementations shall not depend upon:
-
AquaCom telegrams;
-
AquaCom transport;
-
OPC UA server internals.
6. Source tree
The logical source structure is:
src/
├── core/
├── aquacom/
├── history/
├── storage/
├── opcua/
├── diagnostics/
└── host/
The exact language-specific package or project structure may differ, but the architectural responsibilities shall remain equivalent.
7. Dependency direction
Allowed dependencies shall broadly follow:
host
│
┌───────────┼─────────────┐
│ │ │
▼ ▼ ▼
opcua history diagnostics
│ │
│ storage
│ │
└──────┬────┘
▼
core
▲
│
aquacom
The most important rule is:
core
shall not depend upon:
aquacom
opcua
storage technology
8. Core subsystem
The core subsystem contains protocol-independent domain concepts.
Examples include:
StationId
PointId
CurrentValue
HistoricalSample
DataQuality
AcquisitionSource
CommunicationState
StationState
HistorySynchronizationState
The core subsystem defines shared contracts used between other modules.
It shall contain no AquaCom protocol logic.
It shall contain no OPC UA-specific types.
It shall contain no database-specific types.
9. AquaCom subsystem
The AquaCom subsystem contains:
Transport
Protocol codec
Telegram validation
Station/session handling
Live acquisition
Historical acquisition
Protocol diagnostics
Logical structure:
AquaCom Transport
│
▼
Protocol Codec
│
▼
Protocol Operations
│
▼
Station Session
│
├── Live Acquisition
└── Historical Acquisition
Protocol implementation shall be evidence-based.
Undocumented AquaCom behavior shall not be guessed.
10. AquaCom transport
The transport layer is responsible for communication only.
It may support implementations such as:
TCP
Serial
Serial-over-IP
Other supported AquaCom transport
The transport layer shall not interpret process values.
Conceptual interface:
open
close
send
receive
health
11. AquaCom protocol engine
The protocol engine is responsible for:
-
framing;
-
telegram validation;
-
checksum handling;
-
request encoding;
-
response decoding;
-
protocol error interpretation.
Conceptual transformation:
raw bytes
│
▼
AquaCom message
│
▼
logical protocol result
The codec shall be independently testable without a physical AquaCom device.
12. Station/session manager
Each AquaCom station has an independent logical session.
Conceptual station states:
DISABLED
INITIALIZING
CONNECTING
ONLINE
DEGRADED
OFFLINE
RECOVERING
One failing station shall not stop communication with unrelated stations.
The Station Manager owns:
-
station lifecycle;
-
communication status;
-
retries;
-
scheduling;
-
station diagnostics;
-
history recovery coordination.
13. Canonical data model
The gateway uses a protocol-independent canonical model.
13.1 CurrentValue
Conceptually:
CurrentValue
StationId
PointId
Value
DataType
Quality
SourceTimestamp
ReceivedTimestamp
UpdatedTimestamp
AcquisitionSource
13.2 HistoricalSample
Conceptually:
HistoricalSample
StationId
PointId
Value
DataType
Quality
SourceTimestamp
ReceivedTimestamp
AcquisitionSource
AcquisitionId
Historical samples shall retain the timestamp associated with the process state.
14. Timestamp model
The gateway shall distinguish at least:
SourceTimestamp
ReceivedTimestamp
Where applicable also:
UpdatedTimestamp
ServerTimestamp
Their meanings are:
| Timestamp | Meaning |
|---|---|
| SourceTimestamp | Time associated with the value at the source |
| ReceivedTimestamp | Time the gateway received the information |
| UpdatedTimestamp | Time current gateway state was changed |
| ServerTimestamp | Timestamp used by the OPC UA server |
The following must never be assumed:
ReceivedTimestamp = SourceTimestamp
15. Fundamental historical rule
The fundamental historical-data rule is:
A historical sample represents the process at its SourceTimestamp, not at the time the gateway receives the sample.
Example:
Historical value:
SourceTimestamp = 14:05
ReceivedTimestamp = 18:30
The value belongs to history at:
14:05
It shall not become a new current process value at:
18:30
16. Live-data architecture
Live AquaCom values follow:
AquaCom response
│
▼
Protocol decode
│
▼
Point mapping
│
▼
Canonical CurrentValue
│
▼
Current-State Service
│
├────────► OPC UA
│
└────────► Historical pipeline
if live historization is enabled
The Current-State Service maintains the latest accepted value for each configured point.
17. Current-State Service
Responsibilities:
-
maintain the latest current value;
-
reject obsolete current-state updates where applicable;
-
expose current values to OPC UA;
-
notify subscribers of valid changes;
-
preserve quality and timestamps.
Conceptual interface:
update(CurrentValue)
get(PointId)
getAll(StationId)
subscribe(PointId)
Historical backfill shall not directly call update(CurrentValue).
18. Historical-data architecture
Historical AquaCom data follows:
AquaCom history
│
▼
Historical Acquisition Manager
│
▼
Canonical HistoricalSample
│
▼
Historical Pipeline
│
├────────► History Repository
├────────► Storage Sink A
├────────► Storage Sink B
└────────► Other configured destinations
The historical pipeline is independent from OPC UA.
19. Historical Acquisition Manager
The Historical Acquisition Manager is responsible for:
-
determining missing intervals;
-
requesting AquaCom history;
-
processing historical responses;
-
maintaining synchronization state;
-
managing watermarks;
-
performing reconnect/backfill;
-
throttling history retrieval;
-
avoiding interference with live polling.
Live acquisition shall normally have higher communication priority than bulk history recovery.
20. Historical synchronization
Each station may maintain persistent synchronization state.
Conceptually:
StationId
HistoryStreamId
LastCompleteTimestamp
LastAttemptTimestamp
LastSuccessfulTimestamp
SynchronizationState
Example:
12:00 history synchronized
12:03 communication lost
17:24 communication restored
12:00 → 17:24
identified as recovery interval
The gateway then retrieves available AquaCom history for that interval.
21. Watermark rule
A history synchronization watermark shall only advance after the corresponding interval has been successfully handled according to the configured persistence policy.
"Successfully handled" is defined precisely as: the samples of the interval have been durably spooled, meaning the records have been committed to persistent spool storage and would be re-delivered after a restart. Delivery to the final storage destinations is tracked independently through the per-destination acknowledgements described in §24 and does not gate the watermark.
This distinction matters for restart behavior: if the watermark required final delivery, a gateway restart during a storage outage would force re-retrieval of the entire interval from the AquaCom station (or loss of it, if the station has since overwritten its own history). Advancing the watermark on durable spool, combined with at-least-once idempotent delivery, keeps recovery bounded to the spool rather than the field device.
The following is prohibited:
receive historical packet
│
▼
advance watermark
│
▼
storage fails
Preferred behavior is:
receive
↓
validate
↓
persist/durably queue
↓
advance synchronization state
22. Historical pipeline
The historical pipeline shall conceptually perform:
HistoricalSample
│
▼
Validation
│
▼
Normalization
│
▼
Deduplication
│
▼
Durable Spool
│
▼
Distribution
This pipeline provides a stable boundary between acquisition and storage.
Arrival order is not chronological. Live historization produces samples at the current time while backfill delivers older intervals afterwards, so the pipeline must accept samples in arbitrary order relative to SourceTimestamp. Storage adapters shall therefore support out-of-order writes, and historical queries shall order results by SourceTimestamp, never by storage arrival order.
23. Deduplication
The default historical logical identity is:
StationId
+
PointId
+
SourceTimestamp
A stronger AquaCom-provided identifier may be used where verified.
Identical samples shall not create unintended duplicate history.
Conflicting samples sharing the same logical identity shall generate diagnostics.
The default conflict strategy should favor explicit conflict detection rather than silent overwrite.
Deduplication state shall survive gateway restart, at least for the interval of any in-progress synchronization. Otherwise a restart during backfill would cause the already-received portion of the interval to be stored twice. Two implementation options satisfy this: persisting deduplication state alongside the synchronization watermark, or relying on idempotent storage (the at-least-once delivery described in §24) and treating deduplication as an efficiency measure for steady-state operation. The chosen option shall be documented in the relevant ExecPlan.
The deduplication window shall be bounded; an unbounded identity cache violates §51 (resource boundaries).
Deduplication operates on samples in arrival order, which during backfill is generally not chronological order (see §22 ordering note). The implementation shall not assume chronological input.
24. Durable spool
The historical spool provides restart-safe delivery.
Conceptually:
HistoricalSample
│
▼
Persistent spool
│
├────► Repository
├────► Sink A
└────► Sink B
Each destination maintains independent acknowledgement.
Example:
Record 4711
Repository ACK
CentralHistorian ACK
Archive PENDING
The record remains until configured delivery requirements have been fulfilled.
25. History Repository
A History Repository is a queryable historical source.
It provides operations conceptually equivalent to:
store
storeBatch
readRaw
readAtTime
getBounds
health
The repository used by OPC UA Historical Access is selected by configuration.
The OPC UA implementation shall not know whether the repository is:
relational database
time-series database
embedded historian
industrial historian
other queryable implementation
26. Storage Sink
A Storage Sink is a destination receiving historical records.
Conceptual interface:
initialize
write
writeBatch
flush
health
shutdown
A sink does not need to support historical queries.
Examples:
SQL database
time-series database
enterprise historian
file archive
message broker
data lake connector
27. Repository versus sink
These shall remain separate concepts:
Repository
= query historical data
Sink
= receive historical data
One implementation may support both.
Example:
Local historian
Repository: yes
Sink: yes
Archive export
Repository: no
Sink: yes
28. Multiple storage destinations
A historical record may be delivered to multiple independent destinations.
Example:
Historical Pipeline
│
┌───────────────┼────────────────┐
│ │ │
▼ ▼ ▼
Local Repository Central DB Archive
Failure of one destination shall not unnecessarily block successful destinations.
29. OPC UA architecture
The OPC UA subsystem provides northbound access to normalized gateway information.
Logical components:
OPC UA Server
│
├── Namespace Manager
├── Current Value Provider
├── Historical Provider
├── Quality Mapper
├── Diagnostics Provider
└── Security
30. OPC UA current data
Current values are exposed through normal OPC UA Data Access.
Mapping:
CurrentValue.Value
↓
OPC UA Value
CurrentValue.SourceTimestamp
↓
OPC UA SourceTimestamp
Gateway server time
↓
OPC UA ServerTimestamp
CurrentValue.Quality
↓
OPC UA StatusCode
31. OPC UA Historical Access
Historical Access shall query the configured History Repository.
Correct flow:
OPC UA Client
│
│ HistoryRead
▼
OPC UA Server
│
▼
Historical Provider
│
▼
History Repository
│
▼
HistoricalSample[]
│
▼
OPC UA DataValue[]
32. Prohibited HistoryRead architecture
The following architecture is prohibited:
OPC UA HistoryRead
│
▼
AquaCom request
│
▼
wait for RTU
│
▼
OPC UA response
Historical synchronization and historical client access must be decoupled.
33. OPC UA namespace
The default logical namespace shall resemble:
AquaCom
│
├── Gateway
│ ├── Status
│ ├── Version
│ ├── StartTime
│ ├── ConfigurationVersion
│ ├── HistoricalQueueDepth
│ └── Storage
│
└── Stations
│
├── PS001
│ ├── Process
│ │ ├── Level
│ │ ├── Pump01Running
│ │ └── Pump02Running
│ │
│ └── Diagnostics
│ ├── CommunicationState
│ ├── LastCommunication
│ ├── HistoryState
│ └── HistoryWatermark
│
└── PS002
Exact organization may be configurable.
34. Stable OPC UA NodeIds
OPC UA NodeIds shall derive from stable engineering identifiers.
Example:
station/PS001/point/LEVEL
Changing:
Wet well level
to:
Inlet sump level
shall not normally change the NodeId.
Stable NodeIds are required to preserve client configuration.
35. Diagnostics architecture
Diagnostics are separate from process data.
Conceptually:
Diagnostics
│
├── Gateway
│
├── Station
│
├── AquaCom Protocol
│
├── History
│
├── Storage
└── OPC UA
Diagnostics may be exposed through:
-
logs;
-
metrics;
-
OPC UA diagnostic nodes;
-
future management interfaces.
36. Gateway diagnostics
Examples:
GatewayState
Version
ConfigurationVersion
StartTime
Uptime
StationCount
OnlineStationCount
HistoricalQueueDepth
SpoolDiskUsage
OPCUAState
37. Station diagnostics
Examples:
CommunicationState
LastRequest
LastResponse
LastSuccessfulCommunication
ConsecutiveFailures
ProtocolErrors
HistorySynchronizationState
HistoryWatermark
HistoricalBacklog
38. Storage diagnostics
Per destination:
State
LastSuccessfulWrite
LastFailure
PendingRecords
RetryCount
Latency
A storage failure shall be identifiable independently from an AquaCom communication failure.
39. Logging
Structured logging is preferred.
Useful context includes:
timestamp
severity
component
stationId
pointId
operation
correlationId
message
error
Raw AquaCom telegram logging shall be separately configurable.
40. Configuration architecture
Configuration shall be external and machine-readable.
Conceptual structure:
Gateway Configuration
│
├── Gateway
├── AquaCom
├── Stations
├── Points
├── History
├── Storage
├── OPC UA
├── Security
├── Diagnostics
└── Logging
Configuration validation occurs before activation.
41. Station configuration
A station definition contains concepts equivalent to:
StationId
Enabled
Transport
AquaComAddress
ProtocolProfile
LiveAcquisition
HistoricalAcquisition
PointDefinitionSource
Timezone
Station configuration shall not be embedded directly in protocol source code.
42. Point configuration
A point contains concepts equivalent to:
PointId
DisplayName
Description
SourceReference
DataType
EngineeringUnit
Scaling
LiveEnabled
HistoryEnabled
OPCUAEnabled
Historizing
StoragePolicy
PointId shall remain stable even if presentation metadata changes.
43. Security boundaries
The architecture assumes AquaCom is a legacy field protocol.
Security shall therefore be applied around the AquaCom communication environment.
Conceptually:
SCADA / client network
│
▼
Firewall / segmentation
│
▼
AquaCom Gateway
│
▼
OT communication network
│
▼
Site firewall/router/VPN
│
▼
AquaCom RTU
The gateway shall not assume that AquaCom itself provides modern confidentiality, authentication or authorization.
44. OPC UA security
OPC UA security is handled within the OPC UA subsystem.
Production architecture shall support:
application certificates
trusted client management
secure channels
authentication
authorization
encrypted communication
Insecure endpoints shall not be the normal production default.
45. Secrets boundary
Secrets shall not form part of normal version-controlled configuration.
Examples:
database passwords
API tokens
private keys
certificate private keys
These shall be injected through an external secret mechanism.
46. Host subsystem
The host subsystem composes the application.
Responsibilities include:
-
configuration loading;
-
dependency construction;
-
subsystem startup;
-
lifecycle management;
-
shutdown;
-
top-level health state.
The host shall not become a location for protocol or business logic.
47. Startup architecture
Conceptual startup sequence:
Load configuration
│
▼
Validate configuration
│
▼
Load persistent state
│
▼
Initialize storage
│
▼
Initialize historical services
│
▼
Initialize OPC UA
│
▼
Initialize AquaCom stations
│
▼
Start live acquisition
│
▼
Start historical synchronization
A temporary failure of a non-critical secondary storage destination should not necessarily prevent the gateway from starting.
48. Shutdown architecture
Conceptual controlled shutdown:
Stop accepting administrative changes
│
▼
Stop scheduling new acquisition
│
▼
Complete/cancel active transactions safely
│
▼
Persist synchronization state
│
▼
Flush durable state
│
▼
Stop OPC UA
│
▼
Close storage
│
▼
Terminate
49. Restart recovery
After an unclean restart:
Load configuration
│
▼
Recover persistent spool
│
▼
Restore synchronization watermarks
│
▼
Reconnect AquaCom stations
│
▼
Resume live acquisition
│
▼
Resume historical recovery
Live acquisition should resume before large backlog processing.
50. Scheduling priorities
Where AquaCom communication capacity is limited, scheduling shall conceptually prioritize:
1. communication/session health
2. current/live acquisition
3. alarms/events when implemented
4. explicit configuration operations
5. historical backfill
6. low-priority maintenance
Historical synchronization shall be throttleable.
51. Resource boundaries
All queues and caches shall be bounded.
This applies to:
AquaCom request queues
history queues
storage retry queues
OPC UA historical result sets
continuation state
logging buffers
spool storage
Overflow behavior shall be explicit and observable.
52. Testing architecture
The system shall support independent testing of each architectural boundary.
Conceptually:
Protocol Fixtures
│
▼
AquaCom Codec Tests
Simulator
│
▼
Session / Acquisition Tests
Historical Fixtures
│
▼
History Pipeline Tests
Repository
│
▼
OPC UA HA Tests
Current-State Service
│
▼
OPC UA DA Tests
53. AquaCom simulator
The simulator shall permit development without operational AquaCom equipment.
Supported scenarios shall eventually include:
normal live values
normal history
timeouts
disconnects
delayed response
malformed telegram
bad checksum
duplicate history
conflicting history
clock error
reconnect
backfill
The simulator is part of the architecture, not merely a temporary development tool.
54. Protocol evidence architecture
AquaCom implementation is linked to documented evidence.
Relevant repository area:
docs/protocol/
Recommended structure:
aquacom.md
known-operations.md
protocol-gaps.md
test-vectors.md
Every implemented AquaCom behavior should be traceable to:
Specification
Capture
Known-good implementation
Approved test vector
Unknown behavior remains explicitly unresolved.
55. Error isolation
Failures shall remain contained where possible.
Examples:
| Failure | Expected isolation |
|---|---|
| Station A offline | Station B continues |
| Storage A offline | Storage B continues |
| OPC UA client disconnect | Acquisition continues |
| OPC UA server problem | AquaCom acquisition should continue where possible |
| Historical backfill fails | Live acquisition continues |
| Malformed AquaCom telegram | Telegram rejected, station diagnostics updated |
| Secondary storage failure | Durable spool retains pending delivery |
56. Future extension points
The architecture shall permit future addition of:
OPC UA Alarms & Conditions
AquaCom alarms/events
AquaCom commands
setpoint changes
MQTT
REST API
external analytics
central configuration
redundant gateways
high availability
additional history repositories
additional storage sinks
These shall be added behind explicit subsystem interfaces.
57. Future process-control architecture
If control functionality is introduced later, it shall use a separate command pipeline:
Northbound request
│
▼
Authentication
│
▼
Authorization
│
▼
Command validation
│
▼
Command service
│
▼
AquaCom command
│
▼
Confirmation / readback
│
▼
Audit
A direct mapping from arbitrary OPC UA writes to raw AquaCom telegrams is not an acceptable control architecture.
58. Architectural invariants
The following invariants shall hold throughout implementation.
INV-001
AquaCom-specific logic exists only behind the AquaCom abstraction.
INV-002
The canonical model contains no AquaCom telegram representation.
INV-003
The canonical model contains no OPC UA-specific representation.
INV-004
Historical samples do not update current state solely because they were recently retrieved.
INV-005
Historical SourceTimestamp is preserved.
INV-006
OPC UA HistoryRead queries a repository, not an AquaCom device.
INV-007
A storage failure does not directly stop unrelated live AquaCom acquisition.
INV-008
Point identity remains stable across display-name changes.
INV-009
OPC UA NodeIds remain stable across restart and normal upgrades.
INV-010
Unverified AquaCom protocol details are not implemented as guesses.
INV-011
Synchronization state required for recovery is persistent.
INV-012
Historical delivery supports bounded persistent buffering.
INV-013
Historical samples may arrive out of chronological order; storage adapters support out-of-order writes and queries order by SourceTimestamp.
INV-014
The history synchronization watermark advances only on durable spool commit, and restart recovery of undelivered samples is bounded to the spool rather than the field device.
INV-015
Deduplication remains correct across restart; a restart during synchronization does not silently introduce duplicate historical records.
INV-016
A historical record without a usable SourceTimestamp is quarantined with diagnostics, never silently stored as process history.
59. Primary end-to-end data flows
59.1 Live data
AquaCom RTU
│
▼
Transport
│
▼
Protocol Engine
│
▼
Station Manager
│
▼
CurrentValue
│
▼
Current-State Service
│
├────► OPC UA
│
└────► Historical Pipeline
when live historization is enabled
59.2 AquaCom historical recovery
AquaCom RTU
│
▼
Historical Acquisition
│
▼
HistoricalSample
│
▼
Validation
│
▼
Deduplication
│
▼
Durable Spool
│
├────► Repository
├────► Storage A
└────► Storage B
59.3 OPC UA historical request
OPC UA Client
│
▼
HistoryRead
│
▼
OPC UA Historical Provider
│
▼
History Repository
│
▼
HistoricalSample[]
│
▼
OPC UA DataValue[]
60. Reference architecture
The complete reference architecture is:
FIELD / AQUACOM
│
▼
┌─────────────────────┐
│ AquaCom Transport │
└──────────┬──────────┘
│
▼
┌─────────────────────┐
│ Protocol Engine │
└──────────┬──────────┘
│
▼
┌─────────────────────┐
│ Station Manager │
└──────────┬──────────┘
│
▼
┌─────────────────────┐
│ Canonical Model │
└───────┬───────┬─────┘
│ │
LIVE HISTORY
│ │
▼ ▼
┌──────────────┐ ┌──────────────────┐
│Current-State │ │Historical │
│Service │ │Acquisition │
└──────┬───────┘ └────────┬─────────┘
│ │
│ ▼
│ ┌──────────────────┐
│ │Historical │
│ │Pipeline │
│ └────────┬─────────┘
│ │
│ ┌──────────┼───────────┐
│ │ │ │
│ ▼ ▼ ▼
│ Repository Sink A Sink B
│ │
│ │
▼ ▼
┌────────────────────────────┐
│ OPC UA Server │
│ │
│ Data Access │
│ Historical Access │
│ Diagnostics │
└──────────────┬─────────────┘
│
▼
SCADA / Clients
61. Architecture decision summary
The gateway is intentionally designed as an:
AquaCom Integration Gateway
rather than merely an:
AquaCom OPC UA Server
This allows:
-
OPC UA to be replaced or supplemented;
-
storage technology to change;
-
multiple historians to coexist;
-
AquaCom equipment to be gradually retired;
-
other northbound interfaces to be added;
-
historical acquisition to continue independently of OPC UA clients.
The long-term architectural asset is therefore the normalized integration layer and historical recovery mechanism, not any single external interface.
62. Final architectural rule
The most important data rule is:
Historical data is stored and exposed according to when the process value was valid, not when the gateway happened to retrieve it.
The most important protocol rule is:
AquaCom behavior must be based on verified protocol knowledge and must never be invented merely to complete an implementation.
The most important software rule is: