"""Configuration, diagnostic, constant, and firmware-info register bank.
Implements the 0x1000-0x2FFF area of the WAGO 750-362 (manual §11.2.5).
Watchdog registers 0x1000-0x100B are delegated to :class:`ModbusWatchdog`.
"""
from __future__ import annotations
from collections.abc import Callable
from .stats import STATS_REGISTER, STATS_WORD_COUNT, ModbusStatistics
from .watchdog import ModbusWatchdog, RegisterWriteRefused
# --- register addresses -------------------------------------------------------
REG_LED_ERROR_CODE = 0x1020
REG_LED_ERROR_ARG = 0x1021
REG_ANALOG_OUT_BITS = 0x1022
REG_ANALOG_IN_BITS = 0x1023
REG_DIGITAL_OUT_BITS = 0x1024
REG_DIGITAL_IN_BITS = 0x1025
REG_TCP_CONNECTIONS = 0x102A
REG_KBUS_RESET = 0x102B
REG_TCP_IDLE_TIMEOUT = 0x1030
REG_MAC_ID = 0x1031
REG_RESPONSE_DELAY = 0x1037
REG_TOS = 0x1038
REG_MODULE_DIAG = 0x1050
# constants 0x2000-0x2008
CONSTANTS = {
0x2000: 0x0000,
0x2001: 0xFFFF,
0x2002: 0x1234,
0x2003: 0xAAAA,
0x2004: 0x5555,
0x2005: 0x7FFF,
0x2006: 0x8000,
0x2007: 0x3FFF,
0x2008: 0x4000,
}
# firmware info 0x2010-0x2043
REG_FW_REVISION = 0x2010
REG_FW_SERIES = 0x2011
REG_FW_ITEM = 0x2012
REG_FW_MAJOR = 0x2013
REG_FW_MINOR = 0x2014
REG_FW_DESCRIPTION = 0x2020 # up to 16 words
REG_FW_COMPILE_TIME = 0x2021 # up to 8 words
REG_FW_COMPILE_DATE = 0x2022 # up to 8 words
REG_FW_LOADER = 0x2023 # up to 32 words
REG_MODULE_DESC_0_64 = 0x2030 # 65 words
REG_PROCESS_IMAGE_SETTINGS = 0x2035
REG_DIAGNOSTICS = 0x2036
REG_SOFTWARE_RESET = 0x2040 # write 0x55AA/0xAA55
REG_FACTORY_SETTINGS = 0x2043
RESET_KEYS = (0x55AA, 0xAA55)
SERIES_CODE_750 = 0x02EE # 750 dec
COUPLER_CODE_362 = 0x016A # 362 dec
def _string_to_words(text: str, max_words: int) -> list[int]:
"""Pack ASCII into 16-bit words (2 chars/word, high byte first)."""
data = text.encode("ascii", errors="replace")[: 2 * max_words]
data = data.ljust(2 * max_words, b"\x00")
return [int.from_bytes(data[2 * i : 2 * i + 2], "big") for i in range(max_words)]
class ConfigRegisterBank:
"""Read/write dispatch for the 0x1000-0x2FFF configuration area."""
def __init__(
self,
*,
statistics: ModbusStatistics,
watchdog: ModbusWatchdog,
tcp_connection_counter: Callable[[], int],
mac_id: tuple[int, int, int, int, int, int] = (0x00, 0x30, 0xDE, 0x11, 0x22, 0x33),
response_delay_ms: int = 0,
idle_timeout_units: int = 600,
process_image_bits: tuple[int, int, int, int] = (0, 0, 0, 0),
firmware_description: str = "WAGO 750-362 Simulator",
on_software_reset: Callable[[], None] | None = None,
on_kbus_reset: Callable[[], None] | None = None,
) -> None:
# (analog_in_bits, analog_out_bits, digital_in_bits, digital_out_bits)
self._process_image_bits = process_image_bits
self._stats = statistics
self._watchdog = watchdog
self._tcp_connections = tcp_connection_counter
self._mac_id = mac_id
self._response_delay_ms = response_delay_ms
self._idle_timeout_units = idle_timeout_units
self._led_error_code = 0
self._led_error_arg = 0
self._fw = {
REG_FW_REVISION: 0x0001,
REG_FW_SERIES: SERIES_CODE_750,
REG_FW_ITEM: COUPLER_CODE_362,
REG_FW_MAJOR: 0x0000,
REG_FW_MINOR: 0x0001,
}
self._description = _string_to_words(firmware_description, 16)
self._compile_time = _string_to_words("10:00:00", 8)
self._compile_date = _string_to_words("2026-10-03", 8)
self._loader = _string_to_words("boot", 32)
self._module_desc: list[int] = [0] * 65
self._module_diag: tuple[int, int, int] = (0, 0, 0) # module, channel, diag
self._on_software_reset = on_software_reset
self._on_kbus_reset = on_kbus_reset
# -- image geometry (set by the node after module layout) -------------------
def set_process_image_bits(
self, analog_in: int, analog_out: int, digital_in: int, digital_out: int
) -> None:
self._process_image_bits = (analog_in, analog_out, digital_in, digital_out)
def set_module_description(self, text: str) -> None:
self._module_desc = _string_to_words(text, 65)
def set_led_error(self, code: int, argument: int = 0) -> None:
self._led_error_code = code & 0xFFFF
self._led_error_arg = argument & 0xFFFF
def set_module_diagnosis(self, module: int, channel: int, diagnosis: int) -> None:
"""Fault injection for register 0x1050."""
self._module_diag = (module & 0xFFFF, channel & 0xFFFF, diagnosis & 0xFFFF)
@property
def response_delay_ms(self) -> int:
return self._response_delay_ms
@property
def idle_timeout_ms(self) -> int:
return self._idle_timeout_units * 100
# -- register access -----------------------------------------------------------
def read_config(self, address: int, count: int) -> list[int]:
"""Read `count` words starting at `address`.
The 9-word statistics block (0x1029-0x1031) overlaps dedicated
registers in the manual (0x102A connections, 0x1031 MAC-ID):
a read *starting at* 0x1029 returns the statistics block as a
unit; individual addresses keep their dedicated meanings.
"""
out: list[int] = []
if address <= STATS_REGISTER and address + count > STATS_REGISTER:
out.extend(self._read_one(a) for a in range(address, STATS_REGISTER))
n_stats = min(count - len(out), STATS_WORD_COUNT)
out.extend(self._stats.as_words()[:n_stats])
rest_at = STATS_REGISTER + n_stats
out.extend(self._read_one(a) for a in range(rest_at, address + count))
return out
return [self._read_one(a) for a in range(address, address + count)]
def write_config(self, address: int, values: list[int]) -> None:
for i, value in enumerate(values):
self._write_one(address + i, value)
def _read_one(self, address: int) -> int:
# watchdog block
if 0x1000 <= address <= 0x100B:
return self._watchdog.read(address)
# diagnostics
if address == REG_LED_ERROR_CODE:
return self._led_error_code
if address == REG_LED_ERROR_ARG:
return self._led_error_arg
# image sizes
if address == REG_ANALOG_IN_BITS:
return self._process_image_bits[0] & 0xFFFF
if address == REG_ANALOG_OUT_BITS:
return self._process_image_bits[1] & 0xFFFF
if address == REG_DIGITAL_IN_BITS:
return self._process_image_bits[2] & 0xFFFF
if address == REG_DIGITAL_OUT_BITS:
return self._process_image_bits[3] & 0xFFFF
# statistics
if address == STATS_REGISTER:
return self._stats.slave_device_failure # first word
if address == REG_TCP_CONNECTIONS:
return self._tcp_connections()
if address == REG_KBUS_RESET:
return 0
if address == REG_TCP_IDLE_TIMEOUT:
return self._idle_timeout_units
if REG_MAC_ID <= address < REG_MAC_ID + 3:
return self._mac_id_word(address - REG_MAC_ID)
if address == REG_RESPONSE_DELAY:
return self._response_delay_ms
if address == REG_TOS:
return 0
if address == REG_MODULE_DIAG:
return self._module_diag[0]
if REG_MODULE_DIAG < address < REG_MODULE_DIAG + 3:
return self._module_diag[address - REG_MODULE_DIAG]
# constants
if address in CONSTANTS:
return CONSTANTS[address]
# firmware info
if address in self._fw:
return self._fw[address]
if REG_FW_DESCRIPTION <= address < REG_FW_DESCRIPTION + 16:
return self._description[address - REG_FW_DESCRIPTION]
if REG_FW_COMPILE_TIME <= address < REG_FW_COMPILE_TIME + 8:
return self._compile_time[address - REG_FW_COMPILE_TIME]
if REG_FW_COMPILE_DATE <= address < REG_FW_COMPILE_DATE + 8:
return self._compile_date[address - REG_FW_COMPILE_DATE]
if REG_FW_LOADER <= address < REG_FW_LOADER + 32:
return self._loader[address - REG_FW_LOADER]
if REG_MODULE_DESC_0_64 <= address < REG_MODULE_DESC_0_64 + 65:
return self._module_desc[address - REG_MODULE_DESC_0_64]
if address == REG_PROCESS_IMAGE_SETTINGS:
return 0
if address == REG_DIAGNOSTICS:
return 0
# undefined registers within the config area read as 0
return 0
def _mac_id_word(self, index: int) -> int:
"""Word i of the MAC-ID register (0x1031, 3 words).
The register exposes the first 3 MAC bytes as words (one byte per
word, per the manual's 3-word layout for 6-byte MACs).
"""
return self._mac_id[index] << 8
def _write_one(self, address: int, value: int) -> None:
value &= 0xFFFF
if 0x1000 <= address <= 0x100B:
self._watchdog.write(address, value)
return
if address == STATS_REGISTER:
self._stats.handle_reset_write(value)
return
if address == REG_TCP_IDLE_TIMEOUT:
self._idle_timeout_units = value
return
if address == REG_RESPONSE_DELAY:
self._response_delay_ms = value
return
if address == REG_TOS:
return # stored; echo on read is 0 in v1
if address == REG_KBUS_RESET:
if value in RESET_KEYS:
if self._on_kbus_reset:
self._on_kbus_reset()
return
if address == REG_SOFTWARE_RESET:
if value in RESET_KEYS:
if self._on_software_reset:
self._on_software_reset()
return
if address == REG_FACTORY_SETTINGS:
return
# remaining registers are read-only
raise RegisterWriteRefused(f"register {address:#06x} is read-only")