# Example FAT scenario for a pump-station PLC program.
#
# With a REAL PLC under test: run `wago-sim serve` against this node
# configuration; the PLC drives the outputs and the scenario asserts on
# them. Remove the `plugins:` line below — the PLC is the plant.
#
# Headless (no PLC): the plugins line loads an emulated plant model so
# the scenario can be smoke-tested end-to-end before the FAT bench is
# wired.
name: pump_station_fat
description: "Basic FAT round: start button -> pump relay -> valve -> level ramp"
plugins: [plugins.pump_plant.pump_plant] # remove when a real PLC is connected
inputs: # simulated field signals (what the PLC reads)
# module-based addressing: module number is
# 0-based WITHIN ITS TYPE (DI0, DO0, AI0,
# AO0 — FR-4.3.11 v1.5); channel 0-based
start_button: { type: di, module: 0, channel: 0 } # DI0.0
em_stop_ok: { type: di, module: 0, channel: 1 } # DI0.1
level_sensor: { type: ai, module: 0, channel: 0, scale: 0.1 } # AI0.0, level mm -> counts
outputs: # PLC outputs observed by the scenario
pump_relay: { type: do, module: 0, channel: 0 } # DO0.0
valve_open: { type: do, module: 0, channel: 1 } # DO0.1
speed_setpoint: { type: ao, module: 0, channel: 0, scale: 0.1 } # AO0.0
macros:
pulse_start:
- set: { start_button: ON }
- wait: 250ms
- set: { start_button: OFF }
sequence:
# --- startup checks -------------------------------------------------------
- set: { em_stop_ok: ON }
- assert: { label: "pump idle", conditions: { pump_relay: OFF }, within: 1s }
# --- start sequence ---------------------------------------------------------
- macro: pulse_start
- assert: { label: "pump starts", conditions: { pump_relay: ON }, within: 2s }
- assert: { label: "valve opens", conditions: { valve_open: ON }, within: 2s }
# --- process dynamics -------------------------------------------------------
- ramp: { name: level_sensor, to: 8500, over: 30s }
- wait: 31s
- assert: { label: "speed setpoint raised", conditions: { speed_setpoint: ">= 1000" }, within: 3s }
# --- stop sequence ------------------------------------------------------------
- set: { em_stop_ok: OFF }
- assert: { label: "safe state on e-stop", conditions: { pump_relay: OFF, valve_open: OFF }, within: 2s }
- report: PASS