@@ -5,9 +5,9 @@
| | |
|---|---|
| Project | `wago-modbustcp-simulator-py` |
| Version | 1.3 (Draft for review) |
| Version | 1.4 (Draft for review) |
| Date | 2026-10-03 |
| Status | Framework phase; module addressing implemented (FR-4.3.11); service/container deployment implemented (§12); plain-text request tracing implemented (NFR-6.4); clean CLI error handling implemented (NFR-6.5 CLI part); long-duration simulation (§8), bench mode (§9), web UI (§10) and runtime device configuration (§11) requested |
| Status | Framework phase; module addressing implemented (FR-4.3.11); service/container deployment implemented (§12); plain-text request tracing implemented (NFR-6.4); clean CLI error handling implemented (NFR-6.5 CLI part); long-duration simulation (§8), bench mode (§9), web UI (§10), runtime device configuration (§11), multi-vendor device profiles (§13) and additional fieldbus protocols PROFINET/COMLI (§14) requested |
| Target device simulated | WAGO 750-362 / 750-362/0000-0001 FC Modbus TCP (G4) bus coupler |
| Reference documents | `docs/m07500362_xxxxxxxx_0en.pdf` (750-362 Modbus TCP manual), Modbus TCP specification (modbus.org) |
@@ -1129,7 +1129,196 @@ connected PLC sees a controlled fieldbus-node failure rather than a
---
## 13. Roadmap (post-framework)
## 13. Feature Request — Multi-Vendor Device Profiles
> **Status: requested 2026-10-03, not yet planned into a roadmap phase.**
> Simulate additional Modbus TCP bus couplers — other WAGO 750 couplers
> and other brands' Modbus TCP I/O heads — reusing the existing protocol
> stack. This section captures the requirements; it does not commit to
> a schedule.
### 13.1 Motivation
FAT benches test more than one controller and fieldbus family. Today
the simulator is single-device: the 750-362 register map, limits,
watchdog, and statistics are hard-coded across the protocol stack
(`pdu.py` limits, `datastore.py` address dispatch, `server.py`
connection limit and process-area predicate, `registers.py`,
`watchdog.py`, `stats.py`, `trace.py` annotations). The transport layer
(`mbap.py`), PDU codecs, server skeleton, scenario engine, DSL,
plugins, and reporting are protocol-generic and directly reusable.
A second Modbus TCP device multiplies the value of the bench without a
protocol rewrite: the deltas between Modbus TCP devices are — address
maps, configuration areas, watchdog presence/semantics, statistics
blocks, connection limits, and module catalogs with image-layout
rules. These are exactly the facts the device manual provides.
### 13.2 Requirements
- FR-13.2.1: **Device profile abstraction**: extract the per-device
facts into a profile concept covering: supported function codes and
per-FC limits, max concurrent connections, idle-timeout behavior,
process-image address map (reads and writes), read-back mirror rules,
configuration/diagnostic register areas and semantics, watchdog
(presence, register layout, modes), statistics block layout, and
identity/description registers. The 750-362 becomes the first
profile; its behavior must be unchanged after the refactor (the
existing test suite is the regression gate).
- FR-13.2.2: **Scenario-engine independence**: the scenario engine,
DSL, plugins, and reports must remain device-agnostic — they interact
with a node only through the channel model (`ModuleType` /
`Channel` / `ChannelLocation`) and the datastore's set/read surface.
Scenarios must not require changes when a profile is added.
- FR-13.2.3: **Per-vendor module catalogs**: catalogs keyed by brand;
each entry defines word/bit widths and channels. A node config
selects brand + module list; validation must reject cross-brand
module mixes within one node (e.g., a WAGO 750-430 in an ABB S800
station). New catalogs are data-only additions (no engine changes).
- FR-13.2.4: **Process-image layout rules per brand**: layout becomes
a profile parameter (word-first + byte-packed bit modules is the
WAGO §7.3.2.1 rule; other brands may pack differently — e.g.,
byte-per-channel images). The channel model and alias addressing
(FR-4.3.11 module-based and pool-based schemes) must keep working on
top of any layout.
- FR-13.2.5: **Config registers / watchdog / statistics as pluggable
blocks**: implementations following the existing
`registers.py`/`watchdog.py`/`stats.py` pattern, one set per
profile. Devices lacking a Modbus watchdog or statistics block
expose nothing (or an illegal-address exception) there — that is a
device fact, not a simulator limitation.
- FR-13.2.6: **Trace annotations per profile**: `trace.py` address
annotations (currently 750-362 Tables 119–122) must come from the
active profile so verbose tracing stays meaningful for every device.
- FR-13.2.7: **Profile selection**: node config gains a `device:` key
(e.g. `device: wago-750-362`, the default for backward
compatibility); CLI/`WAGO_SIM_NODE` paths unchanged. `wago-sim
validate` must report unknown devices and cross-brand module mixes
as clean errors.
### 13.3 Candidate devices (informative, non-binding)
- WAGO 750 Modbus TCP family beyond the 362 (352/363/860…): same
register-map family — profile effort is mainly constants and
identity registers.
- Other vendors' Modbus TCP I/O heads / controllers (e.g., Phoenix
Contact Inline, Beckhoff BK/BC series): a profile written against
the vendor manual; effort dominated by the address map and
configuration-register semantics.
### 13.4 Acceptance criteria (draft)
1. The 750-362 profile passes the full existing test suite unchanged
after the profile extraction.
2. A second profile (from §13.3) serves a PLC master that reads/writes
its documented process image; identity/description registers match
the vendor manual; the same scenario DSL drives its channels without
modification.
3. Scenarios written for one device run unchanged against another
device with equivalent channel configuration.
4. `wago-sim validate` reports unknown device keys and cross-brand
module mixes with clean one-line errors.
---
## 14. Feature Request — Additional Fieldbus Protocols (PROFINET, COMLI)
> **Status: requested 2026-10-03, not yet planned into a roadmap phase.**
> Extend the simulator beyond Modbus TCP, motivated by ABB AC800M/800xA
> systems and their distributed I/O: PROFINET IO (AC800M PN controllers
> with S800 I/O via CI840-class interface modules) and COMLI (ABB's
> protocol between AC800M controllers and S800/S900 I/O via CI51x/CI522
> communication interfaces, TCP-encapsulated).
### 14.1 Motivation
An AC800M FAT bench talks to its distributed I/O over the protocol the
controller is actually configured for. Simulating the I/O side of
those protocols lets the same scenario engine, datasets (§8), bench
mode (§9), and reporting drive FAT benches for ABB controllers, not
only Modbus TCP masters.
The architecture separates cleanly along the same seams the
multi-vendor profiles (§13) expose: the scenario engine couples to a
node only through the channel model and the datastore's set/read
surface; a new protocol is a new transport + protocol layer binding to
the same process-image core.
### 14.2 Requirements
- FR-14.2.1: **Protocol abstraction**: a protocol binding defines how
the field-side process image is exposed to a master: wire protocol,
address/identifier model, cyclic vs. transactional access, and the
device's diagnostics/alarm model. The simulator core (process image,
scenario engine, plugins, reports) stays protocol-independent.
- FR-14.2.2: **PROFINET IO device simulation** (candidate; scope to be
defined against AC800M PN-controller configuration): simulate the
device side of PROFINET IO — DCP identify/boot, cyclic RT I/O data
exchange for a configured module list, and enough record/identification
data for the IO controller to bring the device into data exchange.
Scope note: a full PROFINET stack is a major undertaking; a
realistic first target is an Ethernet-level RT simulation of one
S800-style station profile with a fixed module list, driven by the
existing deterministic clock and scenario engine.
- FR-14.2.3: **COMLI device simulation** (candidate; scope to be
defined against AC800M/CI51x/CI522 documentation): simulate the
I/O-side endpoint of ABB COMLI over TCP as used between AC800M and
S800/S900 I/O through CI communication interfaces — the
register/point addressing model, cyclic polling, and the diagnostics
responses the CI interface expects. COMLI's request/response
register semantics map naturally onto the datastore's set/read
surface.
- FR-14.2.4: **Shared scenario engine**: scenarios, aliases, macros,
assertions, plugins, and datasets (§8) work unchanged against
protocol bindings; only the channel/identifier model of the target
I/O system is expressed in the node config (module list with
brand-specific article numbers). A scenario must not name wire-level
addresses; alias resolution stays per-device via FR-4.3.11/FR-13.2.4.
- FR-14.2.5: **Trace and diagnostics parity**: per-protocol verbose
tracing equivalent to the Modbus plain-text trace (NFR-6.4):
PROFINET RT frames and COMLI requests decoded in readable form with
device-level annotations; protocol error counters analogous to the
Modbus statistics block.
- FR-14.2.6: **Fault-injection parity** (per protocol): for PROFINET —
frame loss/corruption, device pull/plug, subslot mismatch,
communication/watchdog timeouts (the PN equivalent of the Modbus
watchdog §3.4); for COMLI — request timeouts, malformed messages,
CI-interface failure simulation. These must be scriptable from
scenarios like the Modbus fault paths (§3.6).
- FR-14.2.7: **Deployment parity**: protocol servers run under the
same service/container model (§12): env-var configuration, graceful
shutdown; one container may host multiple protocol bindings for a
node (a station reachable via different protocols in different bench
setups).
### 14.3 Scoping questions (answer before planning)
1. PROFINET: full device stack vs. targeted RT simulation of one
station profile? Which controller-side tooling (e.g., ABB Compact
Builder) must accept the simulated device?
2. COMLI: exact CI51x/CI522 variants in scope; is TCP encapsulation
sufficient, or is the serial CI variant also needed?
3. Are both protocols needed, or is one the realistic FAT target?
(COMLI is far smaller in scope; PROFINET conformance is the larger
effort by an order of magnitude.)
4. Which I/O module families per protocol (S800 modules via
PROFINET/COMLI interfaces; WAGO 750 modules over Modbus as today)?
### 14.4 Acceptance criteria (draft)
1. An AC800M controller (or a protocol-level test master representing
one) establishes data exchange with the simulated I/O station and
reads/writes the documented process data.
2. The existing scenario DSL drives input changes and observes output
reactions through the new protocol binding, unchanged.
3. Verbose tracing shows per-protocol decoded traffic with device
annotations; fault-injection steps behave like the Modbus
equivalents.
4. The 750-362 Modbus behavior is unaffected (regression suite green).
---
## 15. Roadmap (post-framework)
| Phase | Feature |
|---|---|
@@ -1138,11 +1327,14 @@ connected PLC sees a controlled fieldbus-node failure rather than a
| 4 | FAT report generator (HTML/PDF), scenario comparison, template library per project type |
| 5 | Multi-node orchestration (several couplers in one FAT bench), UDP variant, WBM simulation; **web UI (§10)**; **runtime device configuration (§11)**: module hot-configuration with image rebuild, DIP-switch emulation, WBM-equivalent pages, device-state persistence |
| 6 | CI integration: run scenarios headless, export JUnit XML |
| ? | **Multi-vendor device profiles (§13)** and **additional fieldbus protocols PROFINET/COMLI (§14)** — not yet scheduled; phase assignment after §13.3/§14.3 scoping |
---
## 14. References
## 16. References
- WAGO 750-362 manual `m07500362_xxxxxxxx_0en.pdf`, sections 7.2–7.3 (process image), 11.2 (Modbus), 12.2 (module data architecture)
- WAGO I/O System 750 system description `m075xxxxx_xxxxxxxx_0en.pdf`
- MODBUS Application Protocol Specification V1.1b3 / MODBUS TCP specification (modbus.org)
- MODBUS Application Protocol Specification V1.1b3 / MODBUS TCP specification (modbus.org)
- ABB CI51x/CI522 communication interface and S800/S900 I/O documentation (COMLI)
- PROFINET specification (PI, profibus.com) — if PROFINET scope is confirmed