OPC DA Diagnozer — Project Specification
Version: 0.1 (draft) Status: Planning Target platform: Windows only (OPC DA is a COM/DCOM technology)
1. Problem statement
We experience intermittent disconnections and/or high communication latency between a SCADA system and a control system that communicate over OPC DA (Data Access, the COM/DCOM-based predecessor of OPC UA). Today we have no objective evidence to answer the key triage question:
Is the problem in the SCADA host, the network/DCOM layer, the OPC DA server, or the link between the OPC server and the control devices?
OPC DA failure modes are notoriously hard to diagnose because failures surface as generic
HRESULT errors, hung calls with no client-side timeout, or silently degraded item
quality — long before the SCADA operator sees anything.
2. Approach
Deploy an independent, read-only OPC DA reference client that continuously exercises the same path the SCADA uses:
- Connect to the OPC DA server (local or remote via DCOM) from a Windows machine.
- Poll a small, pre-defined list of tags at a fixed interval.
- Measure read round-trip time (RTT), track item quality (GOOD / UNCERTAIN / BAD and subcodes), device timestamps, and connection state.
- Emit structured, timestamped diagnostic events whenever anything deviates from normal — disconnects, slow reads, hung calls, quality degradation, frozen/stale values.
Because the client is independent of the SCADA, its observations provide a reference baseline against which the SCADA's complaints can be triangulated (see §12).
3. Deployment architecture
flowchart LR
subgraph SCADAzone["SCADA zone (or dedicated diag host)"]
DIAG["OPC DA Diagnozer<br/>(Windows service)"]
end
subgraph CTL["Control system / OPC DA server host"]
OPC["OPC DA server<br/>(COM/DCOM out-of-proc)"]
DEV["Control devices / PLC link"]
end
DIAG -- "DCOM reads (RPC 135 + dynamic ports)" --> OPC
OPC -.-> DEV
DIAG -- "Events (JSONL / Event Log / HTTP)" --> OPS["Engineers & monitoring"]
Placement note: run the tool as close to the SCADA machine as possible (same host or same network segment) so its measured latencies are comparable to what the SCADA experiences. Optionally run a second instance next to the OPC server host for differential diagnosis.
4. Goals
- Run unattended as a Windows service (auto-start, SCM crash recovery).
- Connect to a configured OPC DA server (local or remote DCOM) and read a configured tag list.
- Detect and report, with precise timestamps:
- disconnections and reconnects (including DCOM error codes),
- hung / timed-out RPC calls,
- read latencies exceeding thresholds (single spikes, streaks, and trends),
- tags whose quality is BAD or UNCERTAIN (with decoded subcode),
- persistent-bad and flapping (oscillating) quality per tag,
- stale device timestamps / frozen values while quality reports GOOD,
- mass quality degradation (many tags BAD at once → control-link problem).
- Produce durable, machine-readable evidence (structured logs + Windows Event Log + optional HTTP webhook) suitable for incident review and correlation.
- Be strictly read-only and lightweight — must not perturb the system it measures.
5. Non-goals (v1)
- No writes to the OPC server (no
Writecode path at all). - No OPC UA, OPC HDA, or Alarms & Events support.
- No data historian / storage of every sample (only events + periodic summaries).
- No UI/dashboard in v1 (JSONL logs + webhook are enough for Loki/Grafana ingestion).
- No automatic remediation (diagnose only).
6. Detection rules
| ID | Condition | Default rule | Severity |
|---|---|---|---|
| D1 | Connection lost | Any read/connect COM failure | CRITICAL (event incl. decoded HRESULT) |
| D2 | Reconnect succeeded | After D1, reconnect works | INFO (event with outage duration) |
| D3 | Reconnect flapping | > 3 disconnects in 10 min | CRITICAL |
| D4 | Slow poll (spike) | Single read RTT > warn_ms (default 1000) |
WARN |
| D5 | Sustained slow polls | RTT > warn_ms for slow_poll_streak (5) consecutive polls |
CRITICAL |
| D6 | Latency trend | p95 RTT over last window_polls (60) > warn_ms |
WARN |
| D7 | Poll hang | Read call does not return within timeout_ms (5000) — see §10.4 |
CRITICAL (immediate), see recovery behavior |
| D8 | Tag quality → BAD | Any transition into BAD, decoded subcode | WARN (per tag) |
| D9 | Tag quality → UNCERTAIN | Any transition into UNCERTAIN | INFO |
| D10 | Persistent bad tag | Single tag BAD longer than persistent_bad_s (30) |
WARN (escalated from D8) |
| D11 | Quality flapping | > 5 quality transitions for one tag within 10 min | WARN |
| D12 | Stale timestamp | Device timestamp older than max_age_s (120) while quality GOOD |
WARN |
| D13 | Frozen value | expect_change: true tag with unchanged value+timestamp for max_age_s |
WARN |
| D14 | Mass quality degradation | ≥ 50% of monitored tags BAD simultaneously while connection OK | CRITICAL (CONTROL_LINK_DEGRADED — points at OPC-server↔device link, not DCOM) |
| D15 | Heartbeat / summary | Periodic stats snapshot every heartbeat_s (300) |
INFO |
| D16 | Device link down | A configured device-indicator tag reads false, or any quality other than GOOD, or a read error |
CRITICAL per device (DEVICE_LINK_DOWN); D1/D2 do not imply device-link state |
All thresholds are configurable; severities are INFO / WARN / CRITICAL.
6.1 Device connection-indicator tags (D16)
The config names one or more tags as device-link indicators: values the control system maintains that say whether the OPC server can reach the device. The normal (connected) reading is configurable per indicator — conventions differ per control system, so it is never hardcoded:
devices:
- { name: "Conveyor 3", tag: "...Connected" } # any truthy: true/1
- { name: "Pump A", tag: "...PumpAFault", ok_values: [false, 0] } # inverted fault flag
- { name: "Boiler 2", tag: "...State", ok_values: ["RUN"] } # enum/string state
Default ok_values: [true] (boolean connected-flags are the common case).
Value comparison is by string equality on the read value rendered as text
("True", "1", "RUN"), so type quirks across systems cannot cause false
positives; quality must also be GOOD. Semantics (all DOWN cases are logged as
DEVICE_LINK_DOWN):
| Indicator reading | Interpretation |
|---|---|
GOOD + value ∈ ok_values |
Device connected — normal |
GOOD + value ∉ ok_values |
Device link down / fault — CRITICAL (works for inverted fault-flags: a fault 1 is not in [false, 0]) |
| Any quality other than GOOD (BAD/UNCERTAIN) | Something is wrong with the device link — CRITICAL |
| Read error (tag unreadable) | Something is wrong with the device link — CRITICAL |
Device-link state is per indicator tag: the config maps each indicator to a
human-readable device name for the log lines (see config.example.yaml).
Recovery (DEVICE_LINK_UP) is logged when the same indicator reads GOOD with
an ok value again. A value that is neither in ok_values nor a recognized
fault shape still logs DOWN — the normal state is explicit, and everything
else is "not normal" by definition.
Section optionality: tags: and devices: are each optional in the
config — a devices-only setup monitors just the links, a tags-only setup
runs classic quality/latency surveillance. Both empty (or absent) is a
validation error: the tool would read nothing and every heartbeat would
report tags_total: 0.
7. OPC DA quality codes (reference)
OPC DA quality is a 16-bit field. Bits 7–6 of the low byte give the class:
0xC0 GOOD, 0x40 UNCERTAIN, 0x00 BAD. Bits 5–0 are the substatus. Values the tool
decodes and names:
| Code | Meaning |
|---|---|
0xC0 |
GOOD |
0xD8 |
GOOD / local override |
0x44 |
UNCERTAIN / last usable value |
0x40 |
UNCERTAIN (unspecified) |
0x00 |
BAD (unspecified) |
0x04 |
BAD / configuration error |
0x08 |
BAD / not connected |
0x0C |
BAD / device failure |
0x10 |
BAD / sensor failure |
0x14 |
BAD / last known value |
0x18 |
BAD / communication failure |
0x1C |
BAD / out of service |
Remaining UNCERTAIN subcodes (DA 2.05a) are decoded by the same table in quality.py.
Every quality event carries the raw hex code and the decoded name.
Clear-text status rule: wherever a status or quality is reported — JSONL
fields, the text log, Event Log, console — it is written in clear text with
the raw code in parentheses: BAD / communication failure (0x18),
GOOD (0xC0). Nobody should have to decode hex codes by hand, but the raw
code stays for unambiguous correlation with vendor documentation and the
HRESULT table.
8. Event model
Every event is a structured record:
{
"time_utc": "2026-10-07T12:34:56.789Z",
"kind": "QUALITY_BAD",
"severity": "WARN",
"detail": {
"tag": "Channel1.Device1.Counter",
"quality_raw": "0x18",
"quality": "BAD_COMM_FAILURE",
"previous_quality": "GOOD",
"value": 1234.0,
"device_time_utc": "2026-10-07T12:34:55.100Z",
"rtt_ms": 42.1
},
"context": {
"uptime_s": 3600.5,
"reconnects_total": 2,
"rtt_p95_ms": 55.2,
"tags_bad": 3,
"tags_total": 25
}
}
time_utc is always the local client receive time (wall clock), so events remain
comparable even if the remote host's clock is wrong. Device timestamps are reported
alongside and clearly labeled.
9. Outputs (reporters)
| Reporter | Purpose | Notes |
|---|---|---|
| JSONL rotating file | Primary evidence trail | One JSON event per line; rotation by size; default dir %ProgramData%\OPCDA-Diagnozer\logs |
| Plain-text anomaly log | Human-readable evidence | One line per detected anomaly (not heartbeats): timestamp, kind, tag/device, message with clear-text status NAME (0xNN); same rotation scheme as JSONL. See §9.1 for the line format |
| Windows Event Log | Ops visibility | WARN+ only; source OPCDA-Diagnozer |
| Console | Foreground/debug runs | Human-readable |
| HTTP webhook (optional) | Alert integration | POST one JSON event per request, optional bearer token |
Reporters are pluggable (Reporter.emit(event)); a heartbeat event every 5 minutes
proves liveness and enables baseline graphs even when everything is healthy.
The JSONL file stays the machine-readable source of truth; the text log is a
human-first convenience view of the same events — every text line corresponds
to a JSONL record.
9.1 Plain-text anomaly log format
File anomalies-YYYYMMDD.log (daily rotation, size-capped) in the same log
directory. One line per detected anomaly — anomalies only; heartbeats and
reconnect-OK events do not appear here. Clear text first, codes in parentheses:
2026-10-07 14:23:01.123 UTC WARN QUALITY_BAD tag 'Channel1.Device1.Counter' changed GOOD (0xC0) -> BAD / communication failure (0x18)
2026-10-07 14:24:31.500 UTC CRITICAL DEVICE_LINK_DOWN device 'Conveyor 3': link indicator 'Channel1.Device3.Connected' read false (GOOD)
2026-10-07 14:26:02.780 UTC CRITICAL DEVICE_LINK_DOWN device 'Conveyor 3': link indicator 'Channel1.Device3.Connected' quality BAD / not connected (0x08)
2026-10-07 14:27:10.001 UTC CRITICAL POLL_HANG read call hung > 5000 ms; COM thread abandoned and rebuilt
2026-10-07 14:30:00.000 UTC CRITICAL CONTROL_LINK_DEGRADED 12 of 14 monitored tags BAD while connection OK
Fields (pipe-free, fixed order): timestamp SEVERITY KIND message.
Timestamps are the local receive time in UTC (§8). The message carries the
clear-text status with the code between parentheses per §7. A matching
recovery (link back up, quality back to GOOD) is also logged as an anomaly
line, so the log reads as a continuous incident narrative.
10. Operational behavior
10.1 Run as a Windows service
- Registered via pywin32 (
opcda-diagnozer install), auto-start, runs under a dedicated service account (required for DCOM authentication, see §11). - SCM recovery: restart on failure (first/second failure), plus internal watchdog.
10.2 Connection state machine
stateDiagram-v2
[*] --> Connecting
Connecting --> Connected : connect OK
Connecting --> ReconnectWait : COM error
Connected --> ReconnectWait : read error / hang
ReconnectWait --> Connecting : backoff elapsed
Reconnect backoff: exponential 1 s → 2 s → … capped at 60 s. Every disconnect/reconnect pair is an event; outage duration is computed and reported.
10.3 COM apartment handling
All OPC/COM work runs on one dedicated STA thread inside the service process
(pythoncom.CoInitialize() on that thread only). Detectors run on the same thread (pure
Python, cheap); event reporting happens off-thread via a queue so slow I/O never blocks
polling.
10.4 The DCOM hang problem (important)
DCOM/RPC calls have no client-side timeout. If the network path breaks silently (e.g., firewall drops), a read call can block for tens of seconds to minutes without erroring. The tool handles this explicitly:
- A watchdog flags a poll hang (D7) as soon as a call exceeds
timeout_ms. - If the hang exceeds
hard_hang_s(default 120 s), the service abandons the stuck thread and creates a fresh connection on a new thread (staleRPCobjects are released by COM). - Hang events are distinguished from clean disconnects — this is often the smoking gun for silent network drops.
10.5 Safety constraints
- Read-only by construction: no write API is called; the code has no write path.
- Single OPC group, static item list, modest poll rate (default 1 s) to keep added server load negligible.
- Configuration errors fail fast at startup with actionable messages
(
opcda-diagnozer check-configvalidates without connecting… and--probeconnects once and reports).
11. Environment & constraints
| Constraint | Consequence |
|---|---|
| OPC DA is Windows/COM only | Service runs on Windows only (Server 2012 R2 … 2022, Win 10/11) |
OPC DA wrappers are often 32-bit DLLs (OPC DA Automation Wrapper OPCAutomation.dll, Graybox GBDaCtl.dll) |
Python interpreter bitness must match the wrapper DLL — likely 32-bit Python for v1; decision in Phase 0 |
| DCOM security | The service account needs Launch+Activation and Access permissions on the OPC server (via dcomcnfg); account must authenticate across the network (not LocalSystem) |
| Post-2022 Windows DCOM hardening (KB5004442 family) | DCOM activation now requires explicit authentication; legacy OPC setups may fail activation — errors must be reported clearly |
| RPC over TCP | Firewall: TCP 135 + RPC dynamic port range on the server host; misconfig shows up as RPC_S_SERVER_UNAVAILABLE |
| Clock skew | Device timestamps may be misleading; every event also carries local receive time; recommend NTP on both hosts |
12. Diagnostic interpretation matrix (why this tool exists)
| Observation from the Diagnozer | Most likely problem location |
|---|---|
| Clean reads, low RTT, all GOOD — while SCADA still complains | SCADA host itself: per-machine DCOM permissions, CPU/memory saturation, its own group/subscription load |
| Diagnozer also sees disconnects / RPC errors | Shared path: network, firewall, DCOM layer, or OPC server host |
Connection stable, but BAD_COMM_FAILURE on many device tags |
Link between the OPC server and the control devices (downstream of OPC) — not a DCOM/network problem |
| Slow RTT spikes at consistent times of day | Server load pattern; correlate with heartbeat summaries |
| Hangs without errors returned (D7) | Silent network drop (firewall/MTU/NIC) — classic DCOM pitfall |
| One instance (SCADA zone) slow, other (server zone) fast | Network segment between the zones |
13. Acceptance criteria (v1.0)
- AC1 Runs as a service, survives reboot, auto-starts, recovers from a killed process.
- AC2 Detects OPC server process stop within one poll interval (or one hang window for silent drops).
- AC3 Detects injected latency above thresholds within 1–2 polls; event contains measured RTT.
- AC4 Quality transitions produce events with raw code and decoded name.
- AC5 Staleness/freeze detection within tolerance of
max_age_s. - AC6 No OPC writes are ever issued (code review + no write path exists).
- AC7 Events land in JSONL and Event Log; heartbeats appear even when all is healthy.
- AC8 Invalid config fails fast with actionable messages.
- AC9 Footprint ≤ ~50 MB RAM, ~0% CPU while idle-polling on a healthy link.
- AC10 24 h soak against a simulation server: no leaks, correct reconnect accounting.
14. Future extensions (post-v1)
- Async subscription monitoring (
IOPCAsyncIO2DataChange) to compare push vs. poll latency — validates the SCADA's actual callback path. - Per-item latency bisection (read items individually to isolate a slow tag).
- SQLite time-series of samples for post-incident graphing.
- Prometheus exporter / Grafana dashboard.
- Email / Teams / webhook alerting with deduplication.
- Multi-server monitoring in one service.