AquaCom Integration Gateway – Architecture

1. Purpose

This document defines the high-level software architecture of the AquaCom Integration Gateway.

It describes:

  • major system components;

  • dependency direction;

  • data flows;

  • architectural boundaries;

  • live-data handling;

  • historical-data handling;

  • OPC UA integration;

  • storage integration;

  • diagnostics;

  • security boundaries;

  • extension points.

Detailed functional requirements are defined in:


docs/product/software-specification.md

Implementation requirements and Codex-specific development rules are defined in:


docs/product/codex-implementation-specification.md

AGENTS.md

Document roles and precedence. When documents overlap or conflict, the following precedence applies:

  1. docs/product/software-specification.md — the authoritative statement of what the gateway shall do (requirements).
  2. This document — the authoritative statement of how the system is structured to meet those requirements (architecture, boundaries, interfaces).
  3. docs/product/codex-implementation-specification.md — the authoritative statement of how implementation work proceeds (phases, task sizing, test strategy, completion criteria). It restates architectural rules for implementer convenience but does not redefine them.
  4. docs/configuration/configuration-reference.md — the authoritative reference for configuration semantics (field names, defaults, validation rules).
  5. AGENTS.md — the entry-point summary for coding agents; it points to the documents above and never overrides them.

A data contract or interface is defined once in the authoritative document for its role; other documents link to it rather than restating it with different names. Where a contract is currently restated (for historical reasons), the definition in the role-authoritative document wins.

Detailed subsystem architecture is documented under:


docs/architecture/

AquaCom-specific protocol knowledge is documented under:


docs/protocol/


2. System purpose

The AquaCom Integration Gateway provides a modern integration boundary between AquaCom-compatible field equipment and higher-level systems.

The gateway shall:

  • communicate with AquaCom field devices;

  • acquire current process values;

  • retrieve historical process values;

  • normalize AquaCom-specific information into a protocol-independent model;

  • expose current values using OPC UA;

  • expose historical values using OPC UA Historical Access;

  • store historical data in one or more configurable destinations;

  • recover historical information following communication interruptions;

  • provide operational and protocol diagnostics.

The gateway shall not make higher-level systems dependent on AquaCom-specific behavior.


3. Architectural principle

The central architecture is:


AquaCom field device

        │

        ▼

AquaCom Transport

        │

        ▼

AquaCom Protocol Engine

        │

        ▼

Station / Session Manager

        │

        ▼

Canonical Data Model

        │

        ├─────────────────────► Current-State Service

        │                              │

        │                              ▼

        │                        OPC UA Data Access

        │

        └─────────────────────► Historical Pipeline

                                       │

                           ┌───────────┼────────────┐

                           │           │            │

                           ▼           ▼            ▼

                      Repository    Storage A    Storage B

                           │

                           ▼

                   OPC UA Historical Access

The canonical data model forms the boundary between AquaCom-specific functionality and all northbound integrations.


4. Architectural goals

The architecture shall support:

  • protocol isolation;

  • storage independence;

  • stable internal identifiers;

  • stable OPC UA NodeIds;

  • correct handling of source timestamps;

  • reliable history recovery;

  • multiple historical storage destinations;

  • store-and-forward;

  • independent subsystem testing;

  • restart recovery;

  • future replacement of individual technologies;

  • future addition of other northbound interfaces.

The architecture shall avoid tight coupling between:


AquaCom

OPC UA

Database technology

Historian technology

SCADA platform


5. Architectural boundaries

The following boundaries are mandatory.

5.1 AquaCom boundary

Only the AquaCom subsystem may:

  • encode AquaCom telegrams;

  • decode AquaCom telegrams;

  • calculate or verify AquaCom checksums;

  • interpret AquaCom operation codes;

  • interpret AquaCom addressing;

  • interpret AquaCom-specific value formats.

No OPC UA or storage module shall perform AquaCom protocol processing.


5.2 Canonical model boundary

AquaCom data shall be converted into canonical gateway objects before being forwarded to:

  • current-state handling;

  • history handling;

  • OPC UA;

  • storage systems;

  • diagnostics where appropriate.

The canonical model shall remain independent of AquaCom and OPC UA.


5.3 OPC UA boundary

The OPC UA subsystem shall consume canonical gateway information.

It shall not:

  • communicate directly with AquaCom stations;

  • decode telegrams;

  • synchronously request historical data from an RTU;

  • depend upon a particular storage technology.


5.4 Storage boundary

Storage destinations shall receive canonical historical records.

Storage implementations shall not depend upon:

  • AquaCom telegrams;

  • AquaCom transport;

  • OPC UA server internals.


6. Source tree

The logical source structure is:


src/

├── core/

├── aquacom/

├── history/

├── storage/

├── opcua/

├── diagnostics/

└── host/

The exact language-specific package or project structure may differ, but the architectural responsibilities shall remain equivalent.


7. Dependency direction

Allowed dependencies shall broadly follow:


                 host

                  │

      ┌───────────┼─────────────┐

      │           │             │

      ▼           ▼             ▼

   opcua       history      diagnostics

      │           │

      │        storage

      │           │

      └──────┬────┘

             ▼

            core

             ▲

             │

          aquacom

The most important rule is:


core

shall not depend upon:


aquacom

opcua

storage technology


8. Core subsystem

The core subsystem contains protocol-independent domain concepts.

Examples include:


StationId

PointId

CurrentValue

HistoricalSample

DataQuality

AcquisitionSource

CommunicationState

StationState

HistorySynchronizationState

The core subsystem defines shared contracts used between other modules.

It shall contain no AquaCom protocol logic.

It shall contain no OPC UA-specific types.

It shall contain no database-specific types.


9. AquaCom subsystem

The AquaCom subsystem contains:


Transport

Protocol codec

Telegram validation

Station/session handling

Live acquisition

Historical acquisition

Protocol diagnostics

Logical structure:


AquaCom Transport

        │

        ▼

Protocol Codec

        │

        ▼

Protocol Operations

        │

        ▼

Station Session

        │

        ├── Live Acquisition

        └── Historical Acquisition

Protocol implementation shall be evidence-based.

Undocumented AquaCom behavior shall not be guessed.


10. AquaCom transport

The transport layer is responsible for communication only.

It may support implementations such as:


TCP

Serial

Serial-over-IP

Other supported AquaCom transport

The transport layer shall not interpret process values.

Conceptual interface:


open

close

send

receive

health


11. AquaCom protocol engine

The protocol engine is responsible for:

  • framing;

  • telegram validation;

  • checksum handling;

  • request encoding;

  • response decoding;

  • protocol error interpretation.

Conceptual transformation:


raw bytes

    │

    ▼

AquaCom message

    │

    ▼

logical protocol result

The codec shall be independently testable without a physical AquaCom device.


12. Station/session manager

Each AquaCom station has an independent logical session.

Conceptual station states:


DISABLED

INITIALIZING

CONNECTING

ONLINE

DEGRADED

OFFLINE

RECOVERING

One failing station shall not stop communication with unrelated stations.

The Station Manager owns:

  • station lifecycle;

  • communication status;

  • retries;

  • scheduling;

  • station diagnostics;

  • history recovery coordination.


13. Canonical data model

The gateway uses a protocol-independent canonical model.

13.1 CurrentValue

Conceptually:


CurrentValue

    StationId

    PointId

    Value

    DataType

    Quality

    SourceTimestamp

    ReceivedTimestamp

    UpdatedTimestamp

    AcquisitionSource


13.2 HistoricalSample

Conceptually:


HistoricalSample

    StationId

    PointId

    Value

    DataType

    Quality

    SourceTimestamp

    ReceivedTimestamp

    AcquisitionSource

    AcquisitionId

Historical samples shall retain the timestamp associated with the process state.


14. Timestamp model

The gateway shall distinguish at least:


SourceTimestamp

ReceivedTimestamp

Where applicable also:


UpdatedTimestamp

ServerTimestamp

Their meanings are:

| Timestamp | Meaning |

|---|---|

| SourceTimestamp | Time associated with the value at the source |

| ReceivedTimestamp | Time the gateway received the information |

| UpdatedTimestamp | Time current gateway state was changed |

| ServerTimestamp | Timestamp used by the OPC UA server |

The following must never be assumed:


ReceivedTimestamp = SourceTimestamp


15. Fundamental historical rule

The fundamental historical-data rule is:

A historical sample represents the process at its SourceTimestamp, not at the time the gateway receives the sample.

Example:


Historical value:

    SourceTimestamp = 14:05

    ReceivedTimestamp = 18:30

The value belongs to history at:


14:05

It shall not become a new current process value at:


18:30


16. Live-data architecture

Live AquaCom values follow:


AquaCom response

       │

       ▼

Protocol decode

       │

       ▼

Point mapping

       │

       ▼

Canonical CurrentValue

       │

       ▼

Current-State Service

       │

       ├────────► OPC UA

       │

       └────────► Historical pipeline

                  if live historization is enabled

The Current-State Service maintains the latest accepted value for each configured point.


17. Current-State Service

Responsibilities:

  • maintain the latest current value;

  • reject obsolete current-state updates where applicable;

  • expose current values to OPC UA;

  • notify subscribers of valid changes;

  • preserve quality and timestamps.

Conceptual interface:


update(CurrentValue)

get(PointId)

getAll(StationId)

subscribe(PointId)

Historical backfill shall not directly call update(CurrentValue).


18. Historical-data architecture

Historical AquaCom data follows:


AquaCom history

       │

       ▼

Historical Acquisition Manager

       │

       ▼

Canonical HistoricalSample

       │

       ▼

Historical Pipeline

       │

       ├────────► History Repository

       ├────────► Storage Sink A

       ├────────► Storage Sink B

       └────────► Other configured destinations

The historical pipeline is independent from OPC UA.


19. Historical Acquisition Manager

The Historical Acquisition Manager is responsible for:

  • determining missing intervals;

  • requesting AquaCom history;

  • processing historical responses;

  • maintaining synchronization state;

  • managing watermarks;

  • performing reconnect/backfill;

  • throttling history retrieval;

  • avoiding interference with live polling.

Live acquisition shall normally have higher communication priority than bulk history recovery.


20. Historical synchronization

Each station may maintain persistent synchronization state.

Conceptually:


StationId

HistoryStreamId

LastCompleteTimestamp

LastAttemptTimestamp

LastSuccessfulTimestamp

SynchronizationState

Example:


12:00  history synchronized

12:03  communication lost

17:24  communication restored

12:00 → 17:24

       identified as recovery interval

The gateway then retrieves available AquaCom history for that interval.


21. Watermark rule

A history synchronization watermark shall only advance after the corresponding interval has been successfully handled according to the configured persistence policy.

"Successfully handled" is defined precisely as: the samples of the interval have been durably spooled, meaning the records have been committed to persistent spool storage and would be re-delivered after a restart. Delivery to the final storage destinations is tracked independently through the per-destination acknowledgements described in §24 and does not gate the watermark.

This distinction matters for restart behavior: if the watermark required final delivery, a gateway restart during a storage outage would force re-retrieval of the entire interval from the AquaCom station (or loss of it, if the station has since overwritten its own history). Advancing the watermark on durable spool, combined with at-least-once idempotent delivery, keeps recovery bounded to the spool rather than the field device.

The following is prohibited:


receive historical packet

        │

        ▼

advance watermark

        │

        ▼

storage fails

Preferred behavior is:


receive

   ↓

validate

   ↓

persist/durably queue

   ↓

advance synchronization state


22. Historical pipeline

The historical pipeline shall conceptually perform:


HistoricalSample

       │

       ▼

Validation

       │

       ▼

Normalization

       │

       ▼

Deduplication

       │

       ▼

Durable Spool

       │

       ▼

Distribution

This pipeline provides a stable boundary between acquisition and storage.

Arrival order is not chronological. Live historization produces samples at the current time while backfill delivers older intervals afterwards, so the pipeline must accept samples in arbitrary order relative to SourceTimestamp. Storage adapters shall therefore support out-of-order writes, and historical queries shall order results by SourceTimestamp, never by storage arrival order.


23. Deduplication

The default historical logical identity is:


StationId

+

PointId

+

SourceTimestamp

A stronger AquaCom-provided identifier may be used where verified.

Identical samples shall not create unintended duplicate history.

Conflicting samples sharing the same logical identity shall generate diagnostics.

The default conflict strategy should favor explicit conflict detection rather than silent overwrite.

Deduplication state shall survive gateway restart, at least for the interval of any in-progress synchronization. Otherwise a restart during backfill would cause the already-received portion of the interval to be stored twice. Two implementation options satisfy this: persisting deduplication state alongside the synchronization watermark, or relying on idempotent storage (the at-least-once delivery described in §24) and treating deduplication as an efficiency measure for steady-state operation. The chosen option shall be documented in the relevant ExecPlan.

The deduplication window shall be bounded; an unbounded identity cache violates §51 (resource boundaries).

Deduplication operates on samples in arrival order, which during backfill is generally not chronological order (see §22 ordering note). The implementation shall not assume chronological input.


24. Durable spool

The historical spool provides restart-safe delivery.

Conceptually:


HistoricalSample

       │

       ▼

Persistent spool

       │

       ├────► Repository

       ├────► Sink A

       └────► Sink B

Each destination maintains independent acknowledgement.

Example:


Record 4711

Repository         ACK

CentralHistorian   ACK

Archive            PENDING

The record remains until configured delivery requirements have been fulfilled.


25. History Repository

A History Repository is a queryable historical source.

It provides operations conceptually equivalent to:


store

storeBatch

readRaw

readAtTime

getBounds

health

The repository used by OPC UA Historical Access is selected by configuration.

The OPC UA implementation shall not know whether the repository is:


relational database

time-series database

embedded historian

industrial historian

other queryable implementation


26. Storage Sink

A Storage Sink is a destination receiving historical records.

Conceptual interface:


initialize

write

writeBatch

flush

health

shutdown

A sink does not need to support historical queries.

Examples:


SQL database

time-series database

enterprise historian

file archive

message broker

data lake connector


27. Repository versus sink

These shall remain separate concepts:


Repository

    = query historical data

Sink

    = receive historical data

One implementation may support both.

Example:


Local historian

    Repository: yes

    Sink: yes

Archive export

    Repository: no

    Sink: yes


28. Multiple storage destinations

A historical record may be delivered to multiple independent destinations.

Example:


                         Historical Pipeline

                                │

                ┌───────────────┼────────────────┐

                │               │                │

                ▼               ▼                ▼

          Local Repository   Central DB       Archive

Failure of one destination shall not unnecessarily block successful destinations.


29. OPC UA architecture

The OPC UA subsystem provides northbound access to normalized gateway information.

Logical components:


OPC UA Server

    │

    ├── Namespace Manager

    ├── Current Value Provider

    ├── Historical Provider

    ├── Quality Mapper

    ├── Diagnostics Provider

    └── Security


30. OPC UA current data

Current values are exposed through normal OPC UA Data Access.

Mapping:


CurrentValue.Value

        ↓

OPC UA Value

CurrentValue.SourceTimestamp

        ↓

OPC UA SourceTimestamp

Gateway server time

        ↓

OPC UA ServerTimestamp

CurrentValue.Quality

        ↓

OPC UA StatusCode


31. OPC UA Historical Access

Historical Access shall query the configured History Repository.

Correct flow:


OPC UA Client

       │

       │ HistoryRead

       ▼

OPC UA Server

       │

       ▼

Historical Provider

       │

       ▼

History Repository

       │

       ▼

HistoricalSample[]

       │

       ▼

OPC UA DataValue[]


32. Prohibited HistoryRead architecture

The following architecture is prohibited:


OPC UA HistoryRead

       │

       ▼

AquaCom request

       │

       ▼

wait for RTU

       │

       ▼

OPC UA response

Historical synchronization and historical client access must be decoupled.


33. OPC UA namespace

The default logical namespace shall resemble:


AquaCom

│

├── Gateway

│   ├── Status

│   ├── Version

│   ├── StartTime

│   ├── ConfigurationVersion

│   ├── HistoricalQueueDepth

│   └── Storage

│

└── Stations

    │

    ├── PS001

    │   ├── Process

    │   │   ├── Level

    │   │   ├── Pump01Running

    │   │   └── Pump02Running

    │   │

    │   └── Diagnostics

    │       ├── CommunicationState

    │       ├── LastCommunication

    │       ├── HistoryState

    │       └── HistoryWatermark

    │

    └── PS002

Exact organization may be configurable.


34. Stable OPC UA NodeIds

OPC UA NodeIds shall derive from stable engineering identifiers.

Example:


station/PS001/point/LEVEL

Changing:


Wet well level

to:


Inlet sump level

shall not normally change the NodeId.

Stable NodeIds are required to preserve client configuration.


35. Diagnostics architecture

Diagnostics are separate from process data.

Conceptually:


Diagnostics

│

├── Gateway

│

├── Station

│

├── AquaCom Protocol

│

├── History

│

├── Storage

└── OPC UA

Diagnostics may be exposed through:

  • logs;

  • metrics;

  • OPC UA diagnostic nodes;

  • future management interfaces.


36. Gateway diagnostics

Examples:


GatewayState

Version

ConfigurationVersion

StartTime

Uptime

StationCount

OnlineStationCount

HistoricalQueueDepth

SpoolDiskUsage

OPCUAState


37. Station diagnostics

Examples:


CommunicationState

LastRequest

LastResponse

LastSuccessfulCommunication

ConsecutiveFailures

ProtocolErrors

HistorySynchronizationState

HistoryWatermark

HistoricalBacklog


38. Storage diagnostics

Per destination:


State

LastSuccessfulWrite

LastFailure

PendingRecords

RetryCount

Latency

A storage failure shall be identifiable independently from an AquaCom communication failure.


39. Logging

Structured logging is preferred.

Useful context includes:


timestamp

severity

component

stationId

pointId

operation

correlationId

message

error

Raw AquaCom telegram logging shall be separately configurable.


40. Configuration architecture

Configuration shall be external and machine-readable.

Conceptual structure:


Gateway Configuration

│

├── Gateway

├── AquaCom

├── Stations

├── Points

├── History

├── Storage

├── OPC UA

├── Security

├── Diagnostics

└── Logging

Configuration validation occurs before activation.


41. Station configuration

A station definition contains concepts equivalent to:


StationId

Enabled

Transport

AquaComAddress

ProtocolProfile

LiveAcquisition

HistoricalAcquisition

PointDefinitionSource

Timezone

Station configuration shall not be embedded directly in protocol source code.


42. Point configuration

A point contains concepts equivalent to:


PointId

DisplayName

Description

SourceReference

DataType

EngineeringUnit

Scaling

LiveEnabled

HistoryEnabled

OPCUAEnabled

Historizing

StoragePolicy

PointId shall remain stable even if presentation metadata changes.


43. Security boundaries

The architecture assumes AquaCom is a legacy field protocol.

Security shall therefore be applied around the AquaCom communication environment.

Conceptually:


SCADA / client network

        │

        ▼

Firewall / segmentation

        │

        ▼

AquaCom Gateway

        │

        ▼

OT communication network

        │

        ▼

Site firewall/router/VPN

        │

        ▼

AquaCom RTU

The gateway shall not assume that AquaCom itself provides modern confidentiality, authentication or authorization.


44. OPC UA security

OPC UA security is handled within the OPC UA subsystem.

Production architecture shall support:


application certificates

trusted client management

secure channels

authentication

authorization

encrypted communication

Insecure endpoints shall not be the normal production default.


45. Secrets boundary

Secrets shall not form part of normal version-controlled configuration.

Examples:


database passwords

API tokens

private keys

certificate private keys

These shall be injected through an external secret mechanism.


46. Host subsystem

The host subsystem composes the application.

Responsibilities include:

  • configuration loading;

  • dependency construction;

  • subsystem startup;

  • lifecycle management;

  • shutdown;

  • top-level health state.

The host shall not become a location for protocol or business logic.


47. Startup architecture

Conceptual startup sequence:


Load configuration

        │

        ▼

Validate configuration

        │

        ▼

Load persistent state

        │

        ▼

Initialize storage

        │

        ▼

Initialize historical services

        │

        ▼

Initialize OPC UA

        │

        ▼

Initialize AquaCom stations

        │

        ▼

Start live acquisition

        │

        ▼

Start historical synchronization

A temporary failure of a non-critical secondary storage destination should not necessarily prevent the gateway from starting.


48. Shutdown architecture

Conceptual controlled shutdown:


Stop accepting administrative changes

        │

        ▼

Stop scheduling new acquisition

        │

        ▼

Complete/cancel active transactions safely

        │

        ▼

Persist synchronization state

        │

        ▼

Flush durable state

        │

        ▼

Stop OPC UA

        │

        ▼

Close storage

        │

        ▼

Terminate


49. Restart recovery

After an unclean restart:


Load configuration

        │

        ▼

Recover persistent spool

        │

        ▼

Restore synchronization watermarks

        │

        ▼

Reconnect AquaCom stations

        │

        ▼

Resume live acquisition

        │

        ▼

Resume historical recovery

Live acquisition should resume before large backlog processing.


50. Scheduling priorities

Where AquaCom communication capacity is limited, scheduling shall conceptually prioritize:


1. communication/session health

2. current/live acquisition

3. alarms/events when implemented

4. explicit configuration operations

5. historical backfill

6. low-priority maintenance

Historical synchronization shall be throttleable.


51. Resource boundaries

All queues and caches shall be bounded.

This applies to:


AquaCom request queues

history queues

storage retry queues

OPC UA historical result sets

continuation state

logging buffers

spool storage

Overflow behavior shall be explicit and observable.


52. Testing architecture

The system shall support independent testing of each architectural boundary.

Conceptually:


Protocol Fixtures

      │

      ▼

AquaCom Codec Tests

Simulator

      │

      ▼

Session / Acquisition Tests

Historical Fixtures

      │

      ▼

History Pipeline Tests

Repository

      │

      ▼

OPC UA HA Tests

Current-State Service

      │

      ▼

OPC UA DA Tests


53. AquaCom simulator

The simulator shall permit development without operational AquaCom equipment.

Supported scenarios shall eventually include:


normal live values

normal history

timeouts

disconnects

delayed response

malformed telegram

bad checksum

duplicate history

conflicting history

clock error

reconnect

backfill

The simulator is part of the architecture, not merely a temporary development tool.


54. Protocol evidence architecture

AquaCom implementation is linked to documented evidence.

Relevant repository area:


docs/protocol/

Recommended structure:


aquacom.md

known-operations.md

protocol-gaps.md

test-vectors.md

Every implemented AquaCom behavior should be traceable to:


Specification

Capture

Known-good implementation

Approved test vector

Unknown behavior remains explicitly unresolved.


55. Error isolation

Failures shall remain contained where possible.

Examples:

| Failure | Expected isolation |

|---|---|

| Station A offline | Station B continues |

| Storage A offline | Storage B continues |

| OPC UA client disconnect | Acquisition continues |

| OPC UA server problem | AquaCom acquisition should continue where possible |

| Historical backfill fails | Live acquisition continues |

| Malformed AquaCom telegram | Telegram rejected, station diagnostics updated |

| Secondary storage failure | Durable spool retains pending delivery |


56. Future extension points

The architecture shall permit future addition of:


OPC UA Alarms & Conditions

AquaCom alarms/events

AquaCom commands

setpoint changes

MQTT

REST API

external analytics

central configuration

redundant gateways

high availability

additional history repositories

additional storage sinks

These shall be added behind explicit subsystem interfaces.


57. Future process-control architecture

If control functionality is introduced later, it shall use a separate command pipeline:


Northbound request

        │

        ▼

Authentication

        │

        ▼

Authorization

        │

        ▼

Command validation

        │

        ▼

Command service

        │

        ▼

AquaCom command

        │

        ▼

Confirmation / readback

        │

        ▼

Audit

A direct mapping from arbitrary OPC UA writes to raw AquaCom telegrams is not an acceptable control architecture.


58. Architectural invariants

The following invariants shall hold throughout implementation.

INV-001

AquaCom-specific logic exists only behind the AquaCom abstraction.

INV-002

The canonical model contains no AquaCom telegram representation.

INV-003

The canonical model contains no OPC UA-specific representation.

INV-004

Historical samples do not update current state solely because they were recently retrieved.

INV-005

Historical SourceTimestamp is preserved.

INV-006

OPC UA HistoryRead queries a repository, not an AquaCom device.

INV-007

A storage failure does not directly stop unrelated live AquaCom acquisition.

INV-008

Point identity remains stable across display-name changes.

INV-009

OPC UA NodeIds remain stable across restart and normal upgrades.

INV-010

Unverified AquaCom protocol details are not implemented as guesses.

INV-011

Synchronization state required for recovery is persistent.

INV-012

Historical delivery supports bounded persistent buffering.

INV-013

Historical samples may arrive out of chronological order; storage adapters support out-of-order writes and queries order by SourceTimestamp.

INV-014

The history synchronization watermark advances only on durable spool commit, and restart recovery of undelivered samples is bounded to the spool rather than the field device.

INV-015

Deduplication remains correct across restart; a restart during synchronization does not silently introduce duplicate historical records.

INV-016

A historical record without a usable SourceTimestamp is quarantined with diagnostics, never silently stored as process history.


59. Primary end-to-end data flows

59.1 Live data


AquaCom RTU

    │

    ▼

Transport

    │

    ▼

Protocol Engine

    │

    ▼

Station Manager

    │

    ▼

CurrentValue

    │

    ▼

Current-State Service

    │

    ├────► OPC UA

    │

    └────► Historical Pipeline

           when live historization is enabled


59.2 AquaCom historical recovery


AquaCom RTU

    │

    ▼

Historical Acquisition

    │

    ▼

HistoricalSample

    │

    ▼

Validation

    │

    ▼

Deduplication

    │

    ▼

Durable Spool

    │

    ├────► Repository

    ├────► Storage A

    └────► Storage B


59.3 OPC UA historical request


OPC UA Client

    │

    ▼

HistoryRead

    │

    ▼

OPC UA Historical Provider

    │

    ▼

History Repository

    │

    ▼

HistoricalSample[]

    │

    ▼

OPC UA DataValue[]


60. Reference architecture

The complete reference architecture is:


                         FIELD / AQUACOM

                               │

                               ▼

                    ┌─────────────────────┐

                    │ AquaCom Transport   │

                    └──────────┬──────────┘

                               │

                               ▼

                    ┌─────────────────────┐

                    │ Protocol Engine     │

                    └──────────┬──────────┘

                               │

                               ▼

                    ┌─────────────────────┐

                    │ Station Manager     │

                    └──────────┬──────────┘

                               │

                               ▼

                    ┌─────────────────────┐

                    │ Canonical Model     │

                    └───────┬───────┬─────┘

                            │       │

                         LIVE       HISTORY

                            │       │

                            ▼       ▼

                  ┌──────────────┐  ┌──────────────────┐

                  │Current-State │  │Historical        │

                  │Service       │  │Acquisition       │

                  └──────┬───────┘  └────────┬─────────┘

                         │                   │

                         │                   ▼

                         │          ┌──────────────────┐

                         │          │Historical        │

                         │          │Pipeline          │

                         │          └────────┬─────────┘

                         │                   │

                         │        ┌──────────┼───────────┐

                         │        │          │           │

                         │        ▼          ▼           ▼

                         │   Repository   Sink A      Sink B

                         │        │

                         │        │

                         ▼        ▼

                  ┌────────────────────────────┐

                  │        OPC UA Server       │

                  │                            │

                  │ Data Access                │

                  │ Historical Access          │

                  │ Diagnostics                │

                  └──────────────┬─────────────┘

                                 │

                                 ▼

                         SCADA / Clients


61. Architecture decision summary

The gateway is intentionally designed as an:


AquaCom Integration Gateway

rather than merely an:


AquaCom OPC UA Server

This allows:

  • OPC UA to be replaced or supplemented;

  • storage technology to change;

  • multiple historians to coexist;

  • AquaCom equipment to be gradually retired;

  • other northbound interfaces to be added;

  • historical acquisition to continue independently of OPC UA clients.

The long-term architectural asset is therefore the normalized integration layer and historical recovery mechanism, not any single external interface.


62. Final architectural rule

The most important data rule is:

Historical data is stored and exposed according to when the process value was valid, not when the gateway happened to retrieve it.

The most important protocol rule is:

AquaCom behavior must be based on verified protocol knowledge and must never be invented merely to complete an implementation.

The most important software rule is:

AquaCom, canonical data handling, historical persistence and OPC UA shall remain separate architectural concerns.